KR20050005337A - Hybrid System for Ventilation and Air-Conditioning - Google Patents
Hybrid System for Ventilation and Air-Conditioning Download PDFInfo
- Publication number
- KR20050005337A KR20050005337A KR1020030044387A KR20030044387A KR20050005337A KR 20050005337 A KR20050005337 A KR 20050005337A KR 1020030044387 A KR1020030044387 A KR 1020030044387A KR 20030044387 A KR20030044387 A KR 20030044387A KR 20050005337 A KR20050005337 A KR 20050005337A
- Authority
- KR
- South Korea
- Prior art keywords
- air supply
- air
- conduit
- fan
- exhaust
- Prior art date
Links
Classifications
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F11/00—Control or safety arrangements
- F24F11/0001—Control or safety arrangements for ventilation
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F11/00—Control or safety arrangements
- F24F11/62—Control or safety arrangements characterised by the type of control or by internal processing, e.g. using fuzzy logic, adaptive control or estimation of values
- F24F11/63—Electronic processing
- F24F11/64—Electronic processing using pre-stored data
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F8/00—Treatment, e.g. purification, of air supplied to human living or working spaces otherwise than by heating, cooling, humidifying or drying
- F24F8/50—Treatment, e.g. purification, of air supplied to human living or working spaces otherwise than by heating, cooling, humidifying or drying by odorisation
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F2110/00—Control inputs relating to air properties
- F24F2110/10—Temperature
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F2110/00—Control inputs relating to air properties
- F24F2110/20—Humidity
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F2110/00—Control inputs relating to air properties
- F24F2110/50—Air quality properties
- F24F2110/60—Odour
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F2110/00—Control inputs relating to air properties
- F24F2110/50—Air quality properties
- F24F2110/65—Concentration of specific substances or contaminants
- F24F2110/70—Carbon dioxide
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F2221/00—Details or features not otherwise provided for
- F24F2221/14—Details or features not otherwise provided for mounted on the ceiling
Landscapes
- Engineering & Computer Science (AREA)
- Chemical & Material Sciences (AREA)
- Combustion & Propulsion (AREA)
- Mechanical Engineering (AREA)
- General Engineering & Computer Science (AREA)
- Signal Processing (AREA)
- Physics & Mathematics (AREA)
- Fuzzy Systems (AREA)
- Mathematical Physics (AREA)
- Ventilation (AREA)
- Air Conditioning Control Device (AREA)
Abstract
Description
본 발명은 아파트의 고층화 및 고단열, 고기밀화에 따른 급기 및 배기의 문제를 해결하기 위한 환기 시스템을 천정형 공기조화기(냉난방기)와 결합하여, 환기시에는 에너지 절약과 실내 쾌적함을 목적함수로 갖는 제어기의 차압센서의 측정압 피드백에 의한 정압유지용 급기홴의 회전속도 및 급기덕트의 개도, 또는 배기홴의 속도제어를 통하여 실내 환기, 굴뚝 영향 제거, 실내 양압 유지와 에너지 절약을 구현하며, 공기조화기 작동시에는 천정형 공기조화기에 의해 실내의 공기가 흡입되어 냉기 또는 온기로 바뀐 후 다시 환기시스템의 배관덕트를 통해 각 주거공간으로 분배되는 실내 쾌적함 유지의 복합 공조 및 환기 시스템이다.The present invention is combined with a ceiling air conditioner (cooler and air conditioner) to solve the problems of air supply and exhaust due to high rise and high insulation, high density of apartments, energy saving and indoor comfort during ventilation By controlling the rotational speed of the air supply fan for positive pressure maintenance and the opening of the air supply duct or the speed of the exhaust fan by the measured pressure feedback of the differential pressure sensor of the controller, the indoor ventilation, the effect of the chimney is eliminated, the indoor positive pressure is maintained, and the energy saving is realized. It is a complex air-conditioning and ventilation system for maintaining indoor comfort, which is distributed to each living space through the piping duct of the ventilation system after being switched to cold or warm air by inhaling indoor air by the ceiling type air conditioner.
실내 쾌적함의 목적함수로는 주거 공간 소음레벨이 35dBA 이하, 옥타브 주파수레벨이 NC 25 내지 30(여기서 NC는 Noise Criteria이며, 소음허용도라 한다) 사이의 분포이며, 오염농도는 냄새 및 먼지 농도의 기준 이하, 설정 온도 및 상대습도이다.The objective function of indoor comfort is the distribution between the noise level of residential space below 35dBA and the octave frequency level between NC 25 to 30 (where NC is Noise Criteria and noise tolerance), and the pollution concentration is based on odor and dust concentration. Hereafter, it is set temperature and relative humidity.
현재 주택부문에서의 에너지 소비는 국가전체 에너지 소비량의 약 25%를 차지하며, 에너지 소비에 따른 CO2의 발생량은 16.7%를 차지하고 있다. 건물 단위 면적당 에너지 소비량이 상당히 높으며, 경제수준 향상과 더불어 냉난방 수요가 급증하면서 에너지소비량과 CO2의 발생량이 지속적으로 증가할 것으로 여겨진다.Energy consumption in the residential sector currently accounts for about 25% of the country's total energy consumption and emissions of CO 2 from energy consumption accounted for 16.7%. Significantly higher building energy consumption per unit area, with the economy improving, while the level considered to be a surge in demand for air conditioning is constantly increasing amount of energy consumption and CO 2.
최근에는 주택이 고기밀/고단열로 인해 틈새 바람양이 적어져 자연환기가 어려워짐에 따라 면적당 15kW/(hr·m2) 기준 최소환기횟수를 0.5회/hr로 설계하는 추세이다.Recently, as the amount of wind in the house is reduced due to high density of heat and high insulation, natural ventilation becomes difficult, so the minimum ventilation frequency based on 15kW / (hr · m 2 ) is 0.5 times / hr.
미국환기기준인 ASHRAE(Amreica Society of Heating, Refigeration and Air Conditioning Engineers) 규격에 따른 최소 외기 기준은 최대 공기오염농도를 정의한 후, 실내공기환경[IAQ (Indoor Air Quality)]을 유지하기 위한 환기량으로 결정된다. 또한 실내공기환경(IAQ)를 결정하는 방법으로는 환기요구량[CFM(cubic feet per minute)], 급기 중 외기량의 %, 일인당 환기요구량(CFM), 건물면적당 환기요구량, 시간당 환기 횟수[ACH (air change per hour)]가 있다.The minimum outside air standard according to the American Society of Air Conditioning (ASHRAE) standards is defined as the amount of ventilation to maintain the indoor air environment [IAQ (Indoor Air Quality)] after defining the maximum air pollution concentration. do. In addition, the method of determining the indoor air environment (IAQ) includes the ventilation requirement [CFM (cubic feet per minute)], the percentage of outside air supply during the supply, the ventilation demand per person (CFM), the ventilation demand per building area, and the number of ventilation per hour [ACH ( air change per hour)].
주거용 공조시스템은 최근 쾌적한 공조를 위해 개별 공간마다 냉난방을 위한 실내기를 각각 설치하는 추세이며, 특히 이 경우 냉방 부하문제에서 발생하는 효율문제를 해결하기 위한 두개의 압축기를 사용하는 공조시스템은 대한민국 공개특허공보 특2002-0069442에 개시되어 있다. 또한 적절한 환기장치 없이 고기밀화된 주거공간에서 지속적으로 냉난방 공기조화기를 사용할 시 실내 공기의 급속한 오염으로 인해 거주자의 건강에 악영향을 끼치게 되는 문제점이 있다. 이러한 문제의 해결을 위해 최근 천정형 공기조화기 일측과 실외의 사이에 배치된 배기덕트를 이용하여 실내의 오염된 공기의 일부를 강제 배기시켜 실내공기를 쾌적하게 유지시키려는 천정형 공기조화기의 환기시스템이 대한민국 공개특허공보 특2003-0022614에 개시되어 있다.Residential air conditioning systems have recently installed indoor units for air conditioning and heating in individual spaces for comfortable air conditioning, and in this case, an air conditioning system using two compressors to solve the efficiency problem arising from cooling load problems is disclosed in Korea. Publication No. 2002-0069442 is disclosed. In addition, there is a problem that adverse effects on the health of the occupants due to the rapid pollution of indoor air when using the air-conditioning air conditioner continuously in a dense residential space without adequate ventilation. In order to solve this problem, the ventilation system of the ceiling type air conditioner is designed to maintain indoor air comfort by forcibly exhausting some of the indoor polluted air by using an exhaust duct disposed between one side of the ceiling type air conditioner and the outside. It is disclosed in Korean Laid-Open Patent Publication No. 2003-0022614.
하지만, 종래의 공기조화기는 각 주거공간마다 필요한 냉난방을 하게 되므로 편리하지만, 실외기 압축기의 용량 및 컨덴서 열교환기의 용량이 증가하며 냉매배관이 매우 복잡해지고 설치비용이 증가하게 된다. 또한 기밀형 주거공간의 경우 환기문제를 해결하지 않으면 실내 거주자의 건강에 악영향을 끼치게 되며, 기존의 환기시스템과 독립적으로 설치, 운영시 에너지 절약의 측면에서 매우 불리하게 되는 제 1문제점이 야기된다. 이를 해결하기 위한 대안으로서, 천정형 공기조화기 일측과 실외의 사이에 배치된 배기덕트를 이용하여 실내의 오염된 공기의 일부를 강제 배기시켜 실내공기를 쾌적하게 유지시키는 방법은 고기밀화된 공동주택의 경우 배기덕트 입구에 양압이 걸리거나, 실내압이 음압 등으로 변동하는 경우 배기가 적절하게 이루어 지지 않아 환기의 목적에 부합되지 않게 되는 제 2문제점이 야기 된다.However, the conventional air conditioner is convenient because the air conditioning required for each living space is convenient, but the capacity of the outdoor unit compressor and the capacity of the condenser heat exchanger increases, the refrigerant piping is very complicated and the installation cost increases. In addition, in case of airtight residential space, if the ventilation problem is not solved, it will adversely affect the health of the indoor occupants, and cause the first problem that becomes very disadvantageous in terms of energy saving when installed and operated independently of the existing ventilation system. As an alternative to solve this problem, the exhaust air duct disposed between one side of the ceiling air conditioner and the outside is forced to exhaust some of the indoor polluted air to maintain the indoor air comfortably. In this case, when the positive pressure is applied to the exhaust duct inlet, or the room pressure fluctuates to the negative pressure, the second problem is caused because the exhaust is not properly made and does not serve the purpose of ventilation.
본 발명은, 주거용 환기시스템과 공조시스템을 분리하여 독립적으로 설치하는 경우에 발생하는 제 1문제를 극복하기 위해, 공조기 작동시, 환기용 열교환기를 통해 들어오는 급기를 공조기로 흡입되는 실내 공기와 함께 공조기 열교환기를 통과토록 하여, 환기용 현열교환기를 통해 들어오는 급기를, 즉 실내온도(Tr)보다 높은 온도(냉방시) 혹은 낮은 온도(난방시)의 급기를, 다시 냉각하거나 가열하는데 필요한 에너지 만큼을 절약하게 된다.The present invention, in order to overcome the first problem that occurs when the residential ventilation system and the air conditioning system is installed separately from the air conditioning system, during operation of the air conditioner, the air intake air through the heat exchanger for ventilation with the indoor air sucked into the air conditioner Pass through the heat exchanger to supply the incoming air through the sensible heat exchanger for ventilation, that is, the air supply at a temperature higher than the room temperature (T r ) or at a lower temperature (heating), as much as the energy required to cool or heat again. You save.
도 1a에는 환기시스템과 공조시스템을 분리 운영하는 분리형 시스템의 열에너지 유동 체계도가 도시되어 있고, 도 1b에는 그 복합형 시스템의 열에너지 유동의 체계도가 도시되어 있다. 여기서 T∞는 외기 온도, Tc는 냉난방시 공조기 토출온도, Tr은 실내온도, Ti는 열교환기 통과 급기온도, To는 열교환기 통과 배기온도를 나타내며, Q'v는 열교환기 통과 공기유량, Q'a는 공조기 통과 전체 공기유량 그리고 Qao는 공조기 흡입유량을 나타낸다.FIG. 1A shows a thermal energy flow diagram of a separate system for separate operation of a ventilation system and an air conditioning system, and FIG. 1B shows a thermal diagram of heat energy flow of a hybrid system. Where T ∞ is the outside air temperature, T c is the air conditioner discharge temperature during heating and cooling, T r is the room temperature, T i is the heat exchanger air supply temperature, T o is the heat exchanger air exhaust temperature, Q ' v is the heat exchanger air The flow rate, Q ' a, represents the total air flow through the air conditioner and Q ao represents the air intake flow rate.
따라서, 분리형 시스템에서의 단위시간 동안의 실내에너지 변화량은Thus, the amount of change in room energy over a unit time in a separate system is
과 같으며, 복합 시스템에서의 실내에너지 변화량은Is the same as
따라서, 두 시스템사이의 단위 시간당 실내 에너지 차이량은Therefore, the amount of room energy difference per unit time between the two systems is
이 된다. 즉, 환기질량 유량(ρQ'v)과 환기 열교환기에서의 실내측 입출구 엔탈피 차(Cp(Ti-Tr)를 곱한 양과 같게 된다.Becomes That is, it is equal to the quantity multiplied by the ventilation mass flow rate ρQ ' v and the difference between the indoor entrance and exit enthalpy C p (T i -T r ) in the ventilation heat exchanger.
그런데, 도 1b의 복합 시스템과 같이 환기시스템을 통과한 급기량 모두를 덕트 등의 수단으로 열전달 없이 공조기 입구로 배치하는 것은 구조적으로 복잡해 지므로, 본 발명의 도 1c에 도시된 바와 같이 거실의 천정에 설치된 공조기 근처의 환기용 덕트 시스템에 연결된 거실용 디퓨져에서 짧은 회로 (Short Circuit)처럼 바로 공조기 입구로 실내 공기와 함께 유입되도록 한다. 이 경우 환기시스템에 연결된 거실용 배기구 댐퍼가 자동적으로 닫히게 된다.However, it is structurally complicated to arrange all of the air supply passing through the ventilation system to the air conditioner inlet without heat transfer by means of a duct or the like, as shown in the composite system of Figure 1b, so as shown in Figure 1c of the present invention to the ceiling of the living room In the living room diffuser connected to the ventilation duct system near the installed air conditioner, it enters the air conditioner inlet with the indoor air just like a short circuit. In this case, the exhaust vent damper for the living room connected to the ventilation system is automatically closed.
또한, 본 발명은, 제 2 문제점을 해결하기 위해, 즉 국부적으로 오염된 또는 국부적으로 음압된 공간에 국부적으로 급기 및 배기를 증대하기 위해, 도 2에 도시된 바와 같이, Path2를 따른 후, 다시 Path3을 따라서 이동하도록 부스터 홴의 회전속도와 댐퍼의 개방각도를제어함으로써, 급기측에서의 실내공간과 급기홴의 출구 간의 전압력차(P) 및 배기측에서의 실내공간과 실외공간(예를 들면, 복도, 배기관 출구, 굴뚝) 간의 전압력차(P)가Pset을 유지하게 하면서 유량이 Q3가 되게 한다.In addition, the present invention follows the path 2 as shown in FIG. 2 to solve the second problem, that is, to increase the local air supply and exhaust in a locally contaminated or locally negative pressure space. By controlling the rotational speed of the booster 와 and the opening angle of the damper to move along the path 3 again, the voltage difference between the indoor space at the supply side and the outlet of the supply (( P) and the voltage difference between the indoor and outdoor spaces (e.g. corridor, exhaust pipe exit, chimney) on the exhaust side ( P) Maintain P set and let flow rate be Q 3 .
급기 또는 배기 홴에 의해 소비되는 에너지가P×Q에 비례하며 소음파워도 같은 회전수에서P2×Q에 비례하므로, 전압력차를 경로(Path2) 및 경로(Path3)를 순차적으로 거쳐서Pset로 유지시키면, 급기시 및 배기시 경로(Path1)와 같은 비슷한 동력 소비를 갖고서도 낮은 전압력차에서 급기 또는 배기 홴이 작동하게 되므로 공조 시스템에서의 매우 저감된 소음를 유발하며, 다른 공간으로의 유량저감문제도 해결하게 된다.The energy consumed by the supply or exhaust fans Proportional to P × Q and noise power at the same speed Since it is proportional to P 2 × Q, the voltage difference is sequentially passed through the path (Path 2 ) and the path (Path 3 ). Maintaining P set causes the air supply or exhaust fan to operate at low voltage differences with similar power consumption as the supply and exhaust paths (Path 1 ), resulting in very low noise in the air conditioning system, The problem of flow rate reduction of
그러므로, 본 발명의 제 2목적은 고기밀 공동주택의 급배기시 문제가 되는 실내 음압 및 공동배기덕트 굴뚝효과 영향을 제거하며 국부적으로 오염된 공기를 신속하게 환기하여 쾌적성을 확보하며 실내 소음을 최소화하기 위해, 급기 및 배기 부스터 홴의 회전속도 제어와 급기 및 배기 댐퍼 개방각도 제어를 통하여 상기된 구역 간의 전압력차를 일정하게 유지할 수 있도록 복합 부스터 홴을 채용한 저소음, 고효율 능동 급배기 및 공조 시스템을 제공하는 것이다.Therefore, the second object of the present invention is to eliminate the effects of indoor sound pressure and the common exhaust duct chimney effect, which is a problem in the air supply and exhaust of the airtight apartment house, to quickly ventilate locally contaminated air to ensure comfort and to reduce indoor noise. To minimize, low noise, high efficiency active air supply and air conditioning system employing a composite booster fan to maintain a constant voltage difference between the above-mentioned zones through the rotational speed control of the air supply and exhaust booster fan and the air supply and exhaust damper opening angle control. To provide.
도 1a는 종래 기술에 따른 분리형 공조 및 환기 시스템을 도시하는 모식도,Figure 1a is a schematic diagram showing a separate air conditioning and ventilation system according to the prior art,
도 1b는 에너지 효율적면에서 이상적인 복합형 공조 및 환기 시스템을 도시하는 모식도,FIG. 1B is a schematic diagram showing an ideal hybrid air conditioning and ventilation system in energy efficiency;
도 1c는 본 발명에 따른 멀티 복합형 공조 및 환기 시스템을 도시하는 모식도,Figure 1c is a schematic diagram showing a multi-compound air conditioning and ventilation system according to the present invention,
도 2는 본 발명에 따른 공조 및 환기용 부스터 홴의 제어시 성능특성변화를 나타내는 그래프,2 is a graph showing a change in performance characteristics during the control of the booster 용 for air conditioning and ventilation according to the present invention;
도 3은 본 발명에 따른 복합 공조 및 환기시스템의 주요부 구성이 도시된 배치도,3 is a layout view showing the main parts of the composite air conditioning and ventilation system according to the present invention;
도 4는 본 발명에 따른 천정형 공기조화기의 주요부 구성이 도시된 단면도.Figure 4 is a cross-sectional view showing the configuration of the main part of the ceiling air conditioner according to the present invention.
이하, 본 발명에 따른 복합 공조 및 환기 시스템의 실시예를 도 3 및 도 4를 참조하여 설명하면 다음과 같다. 도 3은 본 발명에 따른 복합 공조 및 환기 시스템에 구비되는 천정형 공조조화기를 상기 복합 공조 및 환기 시스템의 주요 구성과 함께 도시하고 있고 그리고 도 4는 도 3의 천정형 공조조화기의 상세도이다.Hereinafter, an embodiment of the complex air conditioning and ventilation system according to the present invention will be described with reference to FIGS. 3 and 4. FIG. 3 shows a ceiling air conditioning unit provided in the complex air conditioning and ventilation system according to the present invention together with the main components of the complex air conditioning and ventilation system, and FIG. 4 is a detailed view of the ceiling air conditioning unit of FIG.
도 3에 도시된 바와 같은, 복합 공조 및 환기 시스템(100)은 출구가 실외에 노출되어 있는 열교환용 배기덕트(ED1) 및 각 욕실(B1, B2)용 배기덕트(ED2,ED3); 상기 배기덕트(ED1)에 접속되어 있고 도시되지 않은 제어부에 의해 제어를 받는 열교환기(H); 상기 열교환기(H)에 접속되어 있고 상기 제어부에 제어를 받아 회전수가 가변가능한 급기용 홴(Fan1) 및 배기용 홴(Fan2), 거실(E) 뿐만 아니라 각 욕실(B1, B2) 및 각 방(R1, R2, R3)에 설치되어, 급기용 홴(Fan1)이 도중에 개재된 주 급기용 도관(L1)의 분기 도관(L1-1, L1-2, L1-3, L1-4, L1-5, L1-6)및 주 급기용 도관(L1)을 경유하여 하여 상기 급기용 홴(Fan1)의 출구에 접속되어 있는 복수개의 디퓨져(F1, F2, F3, F4, F5, F6); 거실(E) 뿐만 아니라 각 방(R1, R2, R3)에 설치되어, 배기용 홴(Fan2)이 도중에 개재된 주 배기용 도관(L2)의 분기 도관(L2-1, L2-2, L2-3, L2-4) 및 주 배기용 도관(L2)을 경유하여 상기 배기용 홴(Fan2)의 입구에 접속되어 있는 복수개의 후드(흡입부)(S1, S2, S3, S4); 상기 각 욕실(B1, B2)용 배기덕트(ED2,ED3)에 접속되어 있는 후드(흡입부)(S5, S6): 상기 디퓨져(F1, F2, F3, F4, F5, F6)들에 접속되어 있는 급기용 분기 도관(L1-1, L1-2, L1-3, L1-4, L1-5, L1-6) 도중에 구비되어 있고 제어부에 제어를 받아 개방각도가 가변가능한 복수개의 모터구동식 댐퍼(D1, D2, D3, D4, D5, D6) 및 상기 후드(S1)에 접속되어 있는 배기용 분기 도관(L2-1) 도중에 구비되어 제어부에 제어를 받아 개방각도가 가변가능한 모터구동식 댐퍼(D9); 거실(E) 뿐만 아니라 각 욕실(B1, B2) 및 각 방(R1, R2, R3)에 설치되어 제어부에 접속되어서 측정 신호를 보내는 실내용 압력검출기(P1. P2, P3, P4, P5, P6); 거실(E)에 설치되어 제어부에 접속되어 측정 신호를 보내는 온도, 먼지, 냄새 및 CO2를검출하는 검출기(V); 그리고 급기용 홴(Fan1)의 출구측의 압력을 검출하기 위해 급기용 홴(Fan1)의 출구측 근방의 주 급기용 도관(L1)에 장착되어 있는 급기용 압력검출기(P7), 실외공간의 압력을 검출하기 위해 배기덕트(ED1) 근방에 설치되어 있는 배기용 압력검출기(P8) 및 바이패스 홴(Fan3)의 출구측의 압력을 검출하기 위해 바이패스 홴의 출구측 근방의 바이패스 도관(L3)에 장착되어 있는 바이패스 압력검출기(P9)를 포함하고 있으며, 그리고 냉난방시 거실(E) 내의 공기가 흡입되어 냉기 혹은 열기로 바뀐 후 다시 거실(E) 뿐만 아니라 상기 급기용 도관(L1)을 통한 각 주거 공간(B1, B2, R1, R2, R3)으로 분배되도록 흡입측이 거실과 유통하고 있고, 토출측이 거실 및 급기용 도관(L1)에 유통되어 있으며, 상기 제어부에 의해 제어를 받는 천정형 공기조화기(200)를 더 포함하고 있다.As shown in FIG. 3, the complex air conditioning and ventilation system 100 includes an exhaust duct ED 1 for heat exchange and an exhaust duct ED 2 and ED 3 for each bathroom B1 and B2 whose outlets are exposed to the outside. ; A heat exchanger (H) connected to the exhaust duct (ED 1 ) and controlled by a controller (not shown); Connected to the heat exchanger (H) and controlled by the control unit (Fan 1 ) and the exhaust fan (Fan 2 ) for the variable speed, the living room (E) as well as each bathroom (B1, B2) and Branch conduits (L1-1, L1-2, L1-3, L1-4) of the main air supply conduit (L1) provided in each of the rooms (R1, R2, R3) with an air supply fan (Fan 1 ) intervening. , L1-5, L1-6) and a plurality of diffusers F1, F2, F3, F4, F5, F6 connected to the outlet of the air supply fan 1 via the main air supply conduit L1. ); Living room (E) as well as each room (R1, R2, R3) is installed on, for an exhaust fan (Fan 2) a branch conduit (L2-1, L2-2, L2 of the main exhaust conduit (L2) for interposing a way A plurality of hoods (suction parts) S1, S2, S3, S4 connected to the inlet of the exhaust fan 2 via -3, L2-4 and the main exhaust conduit L2; Hoods (suction parts) S5 and S6 connected to the exhaust ducts ED 2 and ED 3 for the respective bathrooms B1 and B2: to the diffusers F1, F2, F3, F4, F5 and F6. A plurality of motor drives provided in the middle of connected branch supply conduits (L1-1, L1-2, L1-3, L1-4, L1-5, L1-6) and controlled by the control unit and whose opening angle is variable. The motor-driven type is provided in the middle of the exhaust branch conduit (L2-1) connected to the type dampers (D1, D2, D3, D4, D5, D6) and the hood (S1) and controlled by the controller. Damper D9; Indoor pressure detectors (P1, P2, P3, P4, P5, P6) installed in each bathroom (B1, B2) and each room (R1, R2, R3) as well as the living room (E) and connected to the control unit to send a measurement signal. ); A detector (V) installed in the living room (E) and connected to a control unit to detect temperature, dust, odor, and CO 2 that send a measurement signal; And class appointed fan (Fan 1) class appointed fan (Fan 1) of the outlet side near the main class appointed class appointed pressure is attached to the conduit (L1) detector (P7), the outdoor space to detect the pressure of the outlet side of the Bypass near the outlet side of bypass 홴 for detecting pressure at the outlet side of exhaust pressure detector P8 and bypass 홴 (Fan 3 ) installed near exhaust duct ED1 to detect pressure It includes a bypass pressure detector (P9) mounted to the conduit (L3), and the air in the living room (E) during the heating and cooling is sucked into the cold or hot air and then again the living room (E) as well as the air supply conduit ( The suction side is distributed to the living room so as to be distributed to each living space B1, B2, R1, R2, and R3 through L1), and the discharge side is distributed to the living room and air supply conduit L1, and controlled by the controller. It further includes a ceiling type air conditioner (200) receiving.
여기에서, 상기 급기용 홴(Fan1)이 도중에 개재되어 있는 주 급기용 도관(L1)에는 상기 급기용 홴(Fan1)의 출구측에서 거실측의 분기 도관(L1-1)이 각 욕실(B1, B2) 및 방(R1, R2, R3)측의 급기용 분기 도관(L1-2, L1-3, L1-4, L1-5, L1-6)보다 상류측에 접속되어 있고, 상기 배기용 홴(Fan2)이 도중에 개재되어 있는 주 배기용 도관(L2)에는 상기 배기용 홴(Fan2)의 입구측에서 거실(E)측의 분기 도관(L2-1)이 각 욕실(B1, B2) 및 방(R1, R2, R3)측의 배기용 분기 도관(L2-2, L2-3, L2-4)보다 하류측에 접속되어 있다.Here, the class appointed fan (Fan 1) is interposed in the middle-level appointed main duct (L1) is the class I appointed fan chamber side branch duct (L1-1) of the respective bathroom at the exit side of (Fan 1) with ( B1, B2) and branch air supply branch conduits L1-2, L1-3, L1-4, L1-5, L1-6 on the side of the rooms R1, R2, R3 are connected to the upstream side, and the exhaust In the main exhaust conduit L2 with the fan 2 interposed therein, the branch conduit L2-1 on the living room E side from the inlet side of the exhaust fan 2 is provided for each bathroom B1, It is connected downstream from B2) and exhaust branch conduits L2-2, L2-3, and L2-4 on the sides of the rooms R1, R2, and R3.
또한, 상기 천정형 공기조화기의 토출측 일부는, 상기 제어부에 의해 제어를 받아 회전수가 가변가능한 바이패스 홴(Fan3)이 도중에 개재되어 있는 바이패스 도관(L3)을 경유하여, 상기 거실(E)측 급기용 분기 도관(L1-1)이 상기 주 급기용 도관(L1)에 접속되어 있는 위치보다 하류측에서 그리고 상기 각 욕실(B1, B2) 및 방(R1, R2, R3)측의 급기용 분기 도관(L1-2, L1-3, L1-4, L1-5, L1-6)이 상기 주 급기용 도관(L1)에 접속되어 있는 위치보다 상류측에서 상기 주 급기용 도관(L1)에 접속되어 있다.In addition, a part of the discharge side of the ceiling type air conditioner is controlled by the control unit via the bypass conduit L3 in which a bypass fan (Fan 3 ) whose rotation speed is variable is interposed. For air supply on the downstream side and at each of the bathrooms B1, B2 and the rooms R1, R2, R3 from a position downstream from the position where the branch air supply conduit L1-1 is connected to the main air supply conduit L1. Branch conduits (L1-2, L1-3, L1-4, L1-5, L1-6) are connected to the main air supply conduit L1 at an upstream side from the position where they are connected to the main air supply conduit L1. Connected.
또한, 상기 바이패스 도관(L3)에는 상기 바이패스 홴(Fan3)의 입구측에 상기 제어부에 의해 제어를 받는 모터구동식 바이패스 댐퍼(D8)가 개재되어 있고, 상기 바이패스 도관(L3)이 상기 주 급기용 도관(L1)에 접속되어 있는 위치와 상기 거실(E)측 분기 도관(L1-1)이 상기 주 급기용 도관(L1)에 접속되어 있는 위치 사이의 상기 주 급기용 도관(L1)에는 상기 제어부에 의해 제어를 받는 모터구동식 메인 댐퍼(D7)가 개재되어 있다.In addition, the bypass conduit L3 is provided with a motor-driven bypass damper D 8 controlled by the controller at an inlet side of the bypass fan 3 , and the bypass conduit L3. The main air supply conduit between the position where) is connected to the main air supply conduit L1 and the position where the living room E side branch conduit L1-1 is connected to the main air supply conduit L1. At L1, a motor-driven main damper D 7 controlled by the control unit is interposed.
상기 제어부는 국부적인 급기시, 상기 급기용 홴(Fan1)의 회전속도와 자동 댐퍼의 개방각도를 조절함에 있어, 각 거실(E), 욕실(B1, B2), 방(R1, R2, R3)에 설치된 압력검출기(P1, P2, P3, P4, P5, P6)에 의해 측정된 압력들을 평균하여 평균압력을 구한 다음, 그 평균압력과 급기용 압력검출기(P7)와의 차압이, 도 2에 도시된 바와 같이, 경로(path2), 경로(path3) 순으로 거쳐서 소정된 압력(Pset)으로 유지되게 하고, 그리고 국부적인 배기시, 상기 배기용 홴의 회전속도를 조절함에 있어, 각 거실(E), 욕실(B1, B2), 방(R1, R2, R3)에 설치된 압력검출기(P1, P2, P3, P4, P5, P6)에 의해 측정된 압력들을 평균하여 평균압력을 구한 다음, 그 평균압력과 배기용 압력검출기(P8)와의 차압이 소정된 압력으로 유지되게 되어 있으며,The control unit controls the rotational speed of the fan 용 (Fan 1 ) and the opening angle of the automatic damper at the time of local air supply, and each living room (E), bathroom (B1, B2), room (R1, R2, R3). The average pressure is obtained by averaging the pressures measured by the pressure detectors (P1, P2, P3, P4, P5, and P6) installed in the), and the differential pressure between the average pressure and the pressure supply pressure detector (P7) for air supply is shown in FIG. As shown in the figure, a predetermined pressure (a path (path2), a path3) P set ), and the pressure installed in each living room (E), bathroom (B1, B2), room (R1, R2, R3) to maintain the rotation speed of the exhaust fan for local exhaust. The average pressure is obtained by averaging the pressures measured by the detectors P1, P2, P3, P4, P5, and P6, and the differential pressure between the average pressure and the exhaust pressure detector P8 is maintained at a predetermined pressure. ,
환기 모드시에는 상기 급기용 홴(Fan1) 및 배기용 홴(Fan2)이 작동되며 상기 천정형 공기조화기(200)는 작동중지 되고, 바이패스 댐퍼(D8)는 폐쇄되며, 메인 댐퍼(D7)는 완전히 열리게 된다.In the ventilation mode, the air supply fan (Fan 1 ) and the exhaust fan (Fan 2 ) are operated, the ceiling type air conditioner 200 is stopped, the bypass damper (D 8 ) is closed, and the main damper ( D 7 ) is fully open.
또한, 냉난방모드 시 거실(E)로만 급기가 보내지도록 메인댐퍼(D7)가 폐쇄되며, 거실(E)의 후드용 댐퍼(D9)도 제어부에 의해 차단되어 거실(E)로만 신선한 외기가 공급되며, 천정형 공기조화기(200)로의 유입유량(Qao)은 급기된 공기량(Q'v)과 혼합되어(도 1c참조) 오염농도가 낮아진 상태로 천정형 공기조화기(200)의 열교환기를 거쳐 냉방 혹은 난방 혹은 제습되어 거실로 다시 일부 유량(Q'c)은 토출되고, 나머지 유량(Q'r=Q'v+Q'ao-Q'c)은 댐퍼(D2)를 거쳐 바이패스 홴(Fan3)에 의해 각 욕실 및 방으로 배분된다.In addition, the main damper (D 7 ) is closed so that the air supply is sent only to the living room (E) in the heating and cooling mode, the hood damper (D 9 ) of the living room (E) is also blocked by the control unit so that fresh air only to the living room (E) Supplied to the ceiling air conditioner 200, the inflow flow rate Q ao is mixed with the supplied air amount Q ' v (see FIG. 1C) and the heat exchanger of the ceiling air conditioner 200 is lowered in the pollutant concentration. After cooling, heating or dehumidifying, some of the flow rate (Q ' c ) is discharged back to the living room, and the remaining flow rate (Q' r = Q ' v + Q' ao -Q ' c ) is bypassed through the damper (D 2 ). It is distributed to each bathroom and room by Fan 3 .
이 때, 천정형 공기조화기(200)의 송풍유량(Q'a)은 Q'v+Q'ao및 Q'v+Q'c와 같아지게 되므로, 나머지 공간으로 송풍되는 유량(Q'r)은 Q'v와 이론적으로 같다. 이 때 배기용 홴(Fan2)은 제어부에 접속되어 측정 신호를 보내는 온도, 먼지, 냄새, CO2검출(V)기로부터의 공간 평균적 오염 수치를 기준으로 환기량(Q'v)을 최대치는 Q'a로 하며, 일반적으로는 Q'a의 20~30%로하여 적절한 환기와 함께 에너지 손실이 최소화되도록 한다.At this time, since the blowing flow rate Q ' a of the ceiling type air conditioner 200 becomes equal to Q' v + Q ' ao and Q' v + Q ' c , the flow rate Q' r blown to the remaining space. Is theoretically equivalent to Q ' v . At this time, the exhaust fan (F 2 ) is connected to the control unit, and Q, which maximizes the ventilation amount (Q ' v ) based on the temperature, dust, odor, and the spatial average pollution value from the CO 2 detector (V). such that the energy loss is minimized with proper ventilation in 20-30% of, and in a, generally, Q 'a.
또한, 거실(E)에서의 압력을 양압으로 유지하기 위해, 바이패스 홴(Fan3)의 회전수를 제어하여 Q'v≥Q'r이 되도록 운전한다. 이 때 거실(E) 이외의 개별 공간에서 허용 최대 오염농도 이상의 오염농도 검출 혹은 급속한 냉난방의 필요에 의해 댐퍼(D2~D6)중 하나 이상의 댐퍼의 개도를 증가시키면 다른 공간으로의 유량이 줄어들게 되므로 이를 방지하기 위해 급기하는 공간들의 평균압력과 바이패스 홴(Fan3)의 출구 압력(P9)과의 차이인 차압이 일정하게 유지되도록 정압제어를 수행하여, 추가로 필요한 유량의 공간 이외의 급기량은 고정하여 바이패스 홴(Fan3)의 소비동력을 최소화하는 효과가 있다. 이 경우에는 급기용 홴(Fan1)의 급기량도 바이패스 홴(Fan3)을 통과하는 유량의 증가에 맞추어 증가시켜 거실(E)의 압력을 양압으로 유지시킨다.Further, in order to maintain the pressure in the living room E at a positive pressure, the rotation speed of the bypass Fan (Fan 3 ) is controlled to drive Q ' v ≥ Q' r . At this time, if the opening of one or more dampers of the dampers (D 2 to D 6 ) is increased by detecting the pollution concentration above the maximum allowable contamination level or the need for rapid cooling and heating in an individual space other than the living room (E), the flow to the other space may be reduced. since the mean outside pressure and a bypass fan (Fan 3) outlet pressure (P 9) area of the flow rate required in addition to performing the constant pressure control, so that the differential pressure is kept constant difference with the of space that the air supply in order to prevent this, The air supply is fixed to minimize the power consumption of the bypass fan (Fan 3 ). In this case, the air supply amount of the air supply fan (Fan 1 ) is also increased in accordance with the increase in the flow rate passing through the bypass fan (Fan 3 ) to maintain the pressure in the living room (E) at a positive pressure.
또한, 도 3에 도시된 바와 같이, 실외기(300), 바이패스 도관(L3), 바이패스 홴(Fan3)을 포함하고 있는 상기 천정형 공조기(200)에 대한 실시예를 도 4를 참조하여 설명하면 다음과 같다. 도 4에는 도 3의 천정형 공기 조화기가 200으로서 지시되어 있다. 이 천정형 공기조화기(200)는 저면이 개방되고 천정(1)에 형성된 구멍(2)을 관통하여 천정에 삽입되는 본체(11)와 상기 본체(11) 내에 설치되어 냉매와의 열교환을 통해 공기를 냉각시키는 환형 열교환기(12) 혹은 히터를 통해 공기를 가열시키는 장치와, 거실로 급기된 신선한 공기와 실내 내부의 오염된 공기를 혼합, 흡입하여 상기 열교환기를 통과시킨 후, 일부 유량은 토출구(16)를 경유하여 실내로 다시 토출시키며, 일부는 열교환기 배면에 설치된 덕트(18)를 통해 다시 다른 공간으로 배분되도록 송풍력을 일으키기 위해 상기 환형 열교환기(12)의 방사상 내측방향으로 설치되어 있는 송풍홴(13)과 상기 송풍홴을 회전시키도록 상기본체에 고정된 모터(14)와, 상기 본체의 저면 측에 결합되어 실내와 노출되고 상기 송풍홴(13)과 마주하고 있어 실내측의 공기를 흡입하는 흡입그릴(15)이 중앙에 배치되며 상기 흡입그릴의 둘레 네 방향으로 토출구(16)가 형성된 프런트 패널(17)을 포함하여 구성된다.In addition, as shown in FIG. 3, an embodiment of the ceiling air conditioner 200 including the outdoor unit 300, the bypass conduit L3, and the bypass fan 3 will be described with reference to FIG. 4. Is as follows. 4, the ceiling air conditioner of FIG. 3 is indicated as 200. The ceiling type air conditioner 200 is installed in the main body 11 and the main body 11 through which the bottom surface is opened and penetrates the hole 2 formed in the ceiling 1 and is inserted into the ceiling. After the heat exchanger passes through the heat exchanger by mixing and sucking the air through the annular heat exchanger (12) or a heater for cooling the air, the fresh air supplied to the living room and the indoor contaminated air, some of the flow rate is discharged ( 16 is discharged back into the room via a duct 18, which is installed radially inwardly of the annular heat exchanger 12 so as to generate a blowing force to be distributed to another space through the duct 18 installed on the rear surface of the heat exchanger. A blower fan 13 and a motor 14 fixed to the main body to rotate the blower fan, coupled to the bottom surface side of the main body, are exposed to the room, and face the blower fan 13, thereby providing air to the room side. The suction grille (15) for suction are disposed at the center is configured to include a front panel 17, a discharge port 16 formed in the circumferential direction, four of the suction grille.
또한, 이 복합 공조 및 환기 시스템의 설명에서 주방의 환기에 대한 설명이 생략되었지만, 이 공조 시스템에 주방의 환기를 적용할 경우에, 욕실의 배기와 주방의 배기를 별도의 배기홴을 이용하여 배기시키고, 주방의 급기를 기존의 급기홴 또는 부스터용 급기홴을 이용하는 것은 가능하다.In addition, although the description of the ventilation of the kitchen is omitted from the description of the combined air conditioning and ventilation system, when the kitchen ventilation is applied to the air conditioning system, the exhaust of the bathroom and the exhaust of the kitchen are exhausted by using a separate exhaust fan. In addition, it is possible to use the existing air supply or the booster supply air supply of the kitchen air supply.
본 발명이 상기된 실시예에 한정되는 것은 아니고, 본 발명의 사상 및 범주에 벗어남 없이 다양하게 수정 및 변형할 수 있음은 당해 분야의 통상의 지식을 가진 자에게는 자명한 것이다.It is apparent to those skilled in the art that the present invention is not limited to the above-described embodiments and that various modifications and variations can be made without departing from the spirit and scope of the present invention.
상기와 같이 구성된 본 발명의 복합 공조 및 환기 시스템은 공조시스템 및 환기시스템을 독립적으로 설치, 운영할 경우의 불가피한 에너지 손실을 줄여 주며, 고기밀 주거공간의 양압을 유지하며 최소한의 동력으로 환기시스템의 홴의 속도제어가 가능하며, 멀티형 냉난방기를 사용하지 않고도 한개의 중앙 냉난방기만을 이용하고 전체 주거 공간에 환기시스템용 급배기 덕트를 이용하여 신선하며 냉난방된 공기를 급기하게 되는 효과가 있다.The complex air conditioning and ventilation system of the present invention configured as described above reduces the unavoidable energy loss when installing and operating the air conditioning system and the ventilation system independently, maintains the positive pressure of the high-tight residential space, and maintains the ventilation system with minimal power. It is possible to control the speed of air, and it is effective to supply fresh and cooled air by using only one central air conditioner and air supply duct for ventilation system in the whole living space without using multi type air conditioner.
본 발명의 복합 공조 및 환기 시스템은, 환기시, 국부적으로 오염된, 국부적으로 음압된, 또는 공동배기 덕트 굴뚝효과 영향을 국부적으로 야기하는 공간에 국부적으로 급기 또는 배기를 증대하기 위해, 급기용 홴의 출구측 압력과 실내공간의 평균압력 간의 차압 또는 배기용 홴에 접속된 배기용 도관의 출구 덕트 (예를 들면, 복도, 배기관 출구, 굴뚝)측 압력과 실내공간의 평균압력 간의 차압이 도 2의 경로(Path2)를 따른 후, 다시 경로(Path3)를 따라서 이동하도록 급기용 홴의 회전속도와 급기측의 댐퍼의 개방각도를또는 배기용 홴의 회전속도를 제어함으로써, 상기 압력차가 소정된 압력차(Pset)를 유지하게 하면서 유량이 도 2의 Q3가 되게 한다.The combined air conditioning and ventilation system of the present invention is intended to provide a local air supply or exhaust for augmenting a locally contaminated, locally negatively pressured, or locally causing space in the common exhaust duct chimney effect. The differential pressure between the outlet pressure of the outlet and the average pressure of the interior space or the differential pressure between the outlet duct (for example, corridor, exhaust outlet, chimney) side pressure of the exhaust conduit connected to the exhaust fan and the average pressure of the interior space after along the path (path 2), back path (path 3) the thus by controlling the rotational speed of the star appointed fan rotation speed and the air supply side of the fan for the opening angle or the exhaust of the damper to move, the pressure difference is a predetermined Pressure difference ( P set ) while maintaining the flow rate Q 3 in FIG. 2.
이와 같은 제어에 의해 국부적인 급기시 및 국부적인 배기시 도 2의 경로(Path1)과 같은 비슷한 동력 소비를 갖고서도 낮은 전압력차에서 급기 또는 배기 홴이 작동하게 되므로 공조 시스템에서의 매우 저감된 소음를 유발하며, 다른 공간으로의 유량저감문제도 해결함과 동시에, 실내공간을 신속하게 환기하여 쾌적성을 확보할 수 있게 된다.This control results in very low noise in the air conditioning system because the air supply or exhaust fan operates at a low voltage difference with similar power consumption as in the path 1 of FIG. 2 during local air supply and local exhaust. In addition, it solves the problem of reducing the flow to other spaces and at the same time, it is possible to quickly ventilate the indoor space to ensure comfort.
또한, 냉난방모드 시, 거실로만 급기가 보내지도록 메인댐퍼(D7)가 폐쇄되며, 거실의 흡입부 댐퍼(D9)도 제어부에 의해 차단되어 거실로만 신선한 외기가 공급되며, 급기용 홴(Fan2)은 제어부에 접속되어 측정 신호를 보내는 온도, 먼지, 냄새, CO2검출기로부터의 공간 평균적 오염 수치를 기준으로 환기량 (Q'v)의 최대치는 Q'a로 하며, 일반적으로는 Q'a의 20~30%로 하여 적절한 환기와 함께 에너지 손실이 최소화되도록 한다. 또한 거실에서의 압력을 양압으로 유지하기 위해 바이패스 홴(Fan3)의 회전수를 제어하여 Q'v≥Q'r되도록 운전한다. 이 때 거실 이외의 개별 공간에서 허용 최대 오염농도 이상의 오염농도 검출 혹은 급속한 냉난방의 필요에의해 D2~D6중 하나 이상의 댐퍼의 개도를 증가시키면 다른 공간으로의 유량이 줄어들게 되므로 이를 방지하기 위해 급기하는 공간들의 평균압력과 바이패스 홴(Fan3) 출구 압력(P9)과의 차이인 차압이 일정하게 유지되도록 정압제어를 수행하여, 추가로 필요한 유량의 공간 이외의 급기량은 고정하여 바이패스 홴(Fan3)의 소비동력을 최소화하는 효과가 있다.In addition, in the heating and cooling mode, the main damper (D 7 ) is closed so that the air supply is sent only to the living room, and the suction damper (D 9 ) of the living room is also blocked by the control unit so that fresh air is supplied only to the living room. 2) a temperature is connected to the control unit sends a measurement signal, dust, odor, CO 2 detector space average contamination levels in ventilation rate (Q relative to the from the "maximum value of v) is Q, a, and, in general, Q 'a 20-30% of energy loss should be minimized with proper ventilation. In addition, to maintain the positive pressure in the living room, the speed of the bypass fan (Fan 3 ) is controlled to drive Q ' v ≥ Q' r . In this case, increasing the opening degree of one or more dampers of D 2 ~ D 6 due to the detection of pollution concentrations above the maximum allowable pollution concentration or the need for rapid cooling and heating in individual spaces outside the living room reduces the flow to other spaces. Constant pressure control is carried out so that the differential pressure, which is the difference between the average pressure of the spaces and the bypass fan (P 3 ) outlet pressure (P 9 ), is kept constant. It has the effect of minimizing the consumption power of Fan 3 .
Claims (3)
Priority Applications (1)
Application Number | Priority Date | Filing Date | Title |
---|---|---|---|
KR1020030044387A KR100583004B1 (en) | 2003-07-01 | 2003-07-01 | Hybrid System for Ventilation and Air-Conditioning |
Applications Claiming Priority (1)
Application Number | Priority Date | Filing Date | Title |
---|---|---|---|
KR1020030044387A KR100583004B1 (en) | 2003-07-01 | 2003-07-01 | Hybrid System for Ventilation and Air-Conditioning |
Publications (2)
Publication Number | Publication Date |
---|---|
KR20050005337A true KR20050005337A (en) | 2005-01-13 |
KR100583004B1 KR100583004B1 (en) | 2006-05-23 |
Family
ID=37219738
Family Applications (1)
Application Number | Title | Priority Date | Filing Date |
---|---|---|---|
KR1020030044387A KR100583004B1 (en) | 2003-07-01 | 2003-07-01 | Hybrid System for Ventilation and Air-Conditioning |
Country Status (1)
Country | Link |
---|---|
KR (1) | KR100583004B1 (en) |
Cited By (12)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
KR100730649B1 (en) * | 2006-08-25 | 2007-06-20 | 재단법인 송도테크노파크 | A high efficient system for local air-conditioning by air-curtain |
KR100756441B1 (en) * | 2007-06-11 | 2007-09-07 | (주) 스카이시스템 | Air change system of building and the control method |
KR100838319B1 (en) * | 2007-02-26 | 2008-06-13 | 삼인싸이언스(주) | Variable air ventilation control system and methode using constant face-velocity control |
LT5594B (en) | 2007-11-23 | 2009-09-25 | Ridas Matonis | Ventilation and conditioning system for extra tall buildings |
KR101374542B1 (en) * | 2014-01-13 | 2014-03-17 | (주) 무심종합건축사사무소 | An exhausting control system of contaminant infiltrating into indoor space |
KR101374544B1 (en) * | 2014-01-13 | 2014-03-18 | (주) 무심종합건축사사무소 | An exhausting control system of contaminant infiltrating into indoor space |
KR101374543B1 (en) * | 2014-01-13 | 2014-03-18 | (주) 무심종합건축사사무소 | An exhausting control system of contaminant infiltrating into indoor space |
KR101404433B1 (en) * | 2014-01-13 | 2014-06-11 | (주) 무심종합건축사사무소 | An Exhausting Control System of Contaminant infiltrating into Indoor Space |
WO2021013048A1 (en) * | 2019-07-22 | 2021-01-28 | 世源科技工程有限公司 | Energy-saving ventilation system using process exhaust air |
CN113819544A (en) * | 2021-08-26 | 2021-12-21 | 青岛海尔空调器有限总公司 | Catering area air conditioning system and control method thereof |
KR20230039807A (en) * | 2021-09-13 | 2023-03-22 | 주식회사 대한피엔씨 | Room by room control ventilation system for positive volume for common house and negative pressure room |
KR102658652B1 (en) * | 2023-05-22 | 2024-04-19 | 주식회사 신성엔지니어링 | Desiccant dehumidifier and desiccant dehumidification method using purge-to-purge method |
Families Citing this family (1)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
KR200461411Y1 (en) * | 2009-10-22 | 2012-07-11 | 이은종 | Air ventilation apparatus for exhauting and charging of kitchen |
-
2003
- 2003-07-01 KR KR1020030044387A patent/KR100583004B1/en not_active IP Right Cessation
Cited By (13)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
KR100730649B1 (en) * | 2006-08-25 | 2007-06-20 | 재단법인 송도테크노파크 | A high efficient system for local air-conditioning by air-curtain |
KR100838319B1 (en) * | 2007-02-26 | 2008-06-13 | 삼인싸이언스(주) | Variable air ventilation control system and methode using constant face-velocity control |
KR100756441B1 (en) * | 2007-06-11 | 2007-09-07 | (주) 스카이시스템 | Air change system of building and the control method |
LT5594B (en) | 2007-11-23 | 2009-09-25 | Ridas Matonis | Ventilation and conditioning system for extra tall buildings |
KR101374543B1 (en) * | 2014-01-13 | 2014-03-18 | (주) 무심종합건축사사무소 | An exhausting control system of contaminant infiltrating into indoor space |
KR101374544B1 (en) * | 2014-01-13 | 2014-03-18 | (주) 무심종합건축사사무소 | An exhausting control system of contaminant infiltrating into indoor space |
KR101374542B1 (en) * | 2014-01-13 | 2014-03-17 | (주) 무심종합건축사사무소 | An exhausting control system of contaminant infiltrating into indoor space |
KR101404433B1 (en) * | 2014-01-13 | 2014-06-11 | (주) 무심종합건축사사무소 | An Exhausting Control System of Contaminant infiltrating into Indoor Space |
WO2021013048A1 (en) * | 2019-07-22 | 2021-01-28 | 世源科技工程有限公司 | Energy-saving ventilation system using process exhaust air |
CN113819544A (en) * | 2021-08-26 | 2021-12-21 | 青岛海尔空调器有限总公司 | Catering area air conditioning system and control method thereof |
WO2023024529A1 (en) * | 2021-08-26 | 2023-03-02 | 青岛海尔空调器有限总公司 | Catering area air conditioning system and control method |
KR20230039807A (en) * | 2021-09-13 | 2023-03-22 | 주식회사 대한피엔씨 | Room by room control ventilation system for positive volume for common house and negative pressure room |
KR102658652B1 (en) * | 2023-05-22 | 2024-04-19 | 주식회사 신성엔지니어링 | Desiccant dehumidifier and desiccant dehumidification method using purge-to-purge method |
Also Published As
Publication number | Publication date |
---|---|
KR100583004B1 (en) | 2006-05-23 |
Similar Documents
Publication | Publication Date | Title |
---|---|---|
US11187429B2 (en) | Integrated heat and energy recovery ventilator system | |
KR20170103133A (en) | Ventilator | |
KR100583004B1 (en) | Hybrid System for Ventilation and Air-Conditioning | |
JPH10332181A (en) | Ventilator | |
KR101504077B1 (en) | Under floor air distribution system with integration type air handling unit | |
CN113811720A (en) | PTAC unit with dynamic intelligent air management system | |
JP2018155444A (en) | Air conditioning system and building | |
KR102319066B1 (en) | Integrated system having heating, cooling, and ventilating function in room of building and method thereof | |
KR20180014122A (en) | Ventilator | |
KR20100136799A (en) | Device for ventilating room | |
JPH0979648A (en) | Whole building air conditioning control system | |
JP2002162067A (en) | Air conditioner | |
KR100740711B1 (en) | Control methods for architectural heating and cooling system integrated with ventilation and air cleaning system in residential buildings | |
CN218721938U (en) | All-air conditioning system all-in-one machine | |
JP2004003866A (en) | Ventilation air conditioning system | |
JP3518015B2 (en) | Ventilation air conditioner | |
KR102305958B1 (en) | Eco-friendly cooling and heating ventilation integrated ceiling condition unit | |
JPH037821A (en) | Air conditioner | |
KR101474211B1 (en) | Apparatus for air conditioning per room in high-rise buildings | |
KR20020020392A (en) | water cooling type air conditioner in high apartment | |
JP3095201B2 (en) | Air conditioner | |
JPH0462354A (en) | Air conditioner | |
JP2921405B2 (en) | Air conditioner | |
WO2023229003A1 (en) | Air conditioning system | |
JP2019039602A (en) | Air conditioning system |
Legal Events
Date | Code | Title | Description |
---|---|---|---|
A201 | Request for examination | ||
E902 | Notification of reason for refusal | ||
E701 | Decision to grant or registration of patent right | ||
GRNT | Written decision to grant | ||
FPAY | Annual fee payment |
Payment date: 20131112 Year of fee payment: 8 |
|
FPAY | Annual fee payment |
Payment date: 20140624 Year of fee payment: 9 |
|
LAPS | Lapse due to unpaid annual fee |