KR20000057057A - Air-conditioner - Google Patents
Air-conditioner Download PDFInfo
- Publication number
- KR20000057057A KR20000057057A KR1019990057616A KR19990057616A KR20000057057A KR 20000057057 A KR20000057057 A KR 20000057057A KR 1019990057616 A KR1019990057616 A KR 1019990057616A KR 19990057616 A KR19990057616 A KR 19990057616A KR 20000057057 A KR20000057057 A KR 20000057057A
- Authority
- KR
- South Korea
- Prior art keywords
- temperature
- compressor
- heat exchanger
- target discharge
- refrigerant
- Prior art date
Links
Classifications
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F11/00—Control or safety arrangements
- F24F11/30—Control or safety arrangements for purposes related to the operation of the system, e.g. for safety or monitoring
- F24F11/41—Defrosting; Preventing freezing
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F11/00—Control or safety arrangements
- F24F11/30—Control or safety arrangements for purposes related to the operation of the system, e.g. for safety or monitoring
- F24F11/46—Improving electric energy efficiency or saving
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F11/00—Control or safety arrangements
- F24F11/30—Control or safety arrangements for purposes related to the operation of the system, e.g. for safety or monitoring
- F24F11/49—Control or safety arrangements for purposes related to the operation of the system, e.g. for safety or monitoring ensuring correct operation, e.g. by trial operation or configuration checks
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F11/00—Control or safety arrangements
- F24F11/62—Control or safety arrangements characterised by the type of control or by internal processing, e.g. using fuzzy logic, adaptive control or estimation of values
- F24F11/63—Electronic processing
- F24F11/64—Electronic processing using pre-stored data
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F11/00—Control or safety arrangements
- F24F11/70—Control systems characterised by their outputs; Constructional details thereof
- F24F11/80—Control systems characterised by their outputs; Constructional details thereof for controlling the temperature of the supplied air
- F24F11/86—Control systems characterised by their outputs; Constructional details thereof for controlling the temperature of the supplied air by controlling compressors within refrigeration or heat pump circuits
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F2110/00—Control inputs relating to air properties
- F24F2110/10—Temperature
Landscapes
- Engineering & Computer Science (AREA)
- Chemical & Material Sciences (AREA)
- Combustion & Propulsion (AREA)
- Mechanical Engineering (AREA)
- General Engineering & Computer Science (AREA)
- Air Conditioning Control Device (AREA)
Abstract
Description
본 발명은, 냉동사이클을 구성하는 콤프레서, 응축기, 감압장치(전동 팽창밸브), 증발기 등의 실내유니트와 실외유니트로 나누어 탑재한 분리형 공기조화기에 관한 것이다.The present invention relates to a separate type air conditioner installed by dividing a unit into an outdoor unit and an outdoor unit such as a compressor, a condenser, a pressure reducing device (electric expansion valve), and an evaporator constituting a refrigeration cycle.
실내의 공기를 조화시키는 공기조화기(이하「에어컨」으로 약기함)에서는, 실내유니트와 실외유니트 사이에 형성되어 있는 냉동사이클 중을 냉매가 순환하므로서, 실내유니트에서 배출하는 공기의 온도를 조절하고 있다.In an air conditioner (hereafter abbreviated as "air conditioner") that harmonizes indoor air, the refrigerant circulates in the refrigeration cycle formed between the indoor unit and the outdoor unit, thereby controlling the temperature of the air discharged from the indoor unit. have.
이와같은 에어컨은, 냉동사이클 중에 설치한 전동 팽창밸브의 개방도를 제어하는 것에 의해, 실내유니트에 설치된 열교환기(냉방운전시는 증발기로서 작용하고, 또 난방운전시에는 응축기로서 작용하는)의 냉방량, 난방량을 제어하도록 되어있다.Such an air conditioner controls the degree of opening of the electric expansion valve installed in the refrigeration cycle, thereby cooling the heat exchanger installed in the indoor unit (acting as an evaporator during cooling operation and as a condenser during heating operation). Volume and heating rate are controlled.
상기 에어컨에서는, 콤프레서로부터 토출되는 냉매의 목표온도인 목표배출온도를 설정하고, 콤프레서로부터 토출되는 냉매의 온도(배출온도)를 이 목표배출온도가 되도록 전동 팽창밸브를 제어하고 있다.In the air conditioner, the target discharge temperature, which is the target temperature of the refrigerant discharged from the compressor, is set, and the electric expansion valve is controlled so that the temperature (discharge temperature) of the refrigerant discharged from the compressor becomes the target discharge temperature.
그런데, 상기의 목표배출온도 만으로 전동 팽창밸브를 제어하는 경우, 냉방 모드로 운전하고 있을 때에 증발기의 온도저하로 냉매압력이 저하하면, 그 반동으로 실내유니트의 열교환기 출구부근의 온도가 상승하는(열교환기가 건조하기 시작하는) 일이 있다.However, in the case where the electric expansion valve is controlled only by the target discharge temperature, when the refrigerant pressure decreases due to the temperature decrease of the evaporator while operating in the cooling mode, the reaction temperature increases near the heat exchanger outlet of the indoor unit ( Heat exchangers begin to dry).
실내유니트의 열교환기에 건조가 발생하면, 이 부분에서의 공기의 냉각(및 제습)이 행해지지 않게 되어 송풍용 크로스 플로우 팬에 결로가 생겨 물방울이 부착되는 서리부착이 발생한다.When drying occurs in the heat exchanger of the indoor unit, cooling (and dehumidification) of the air at this part is not performed, and dew condensation occurs in the crossflow fan for blowing, causing frosting to which water droplets adhere.
이 서리부착이 발생한 상태로 송풍을 하게 되면, 수분이 실내유니트내에 비산하거나 배출구로부터 실내로 배출되어 버리는 문제가 발생한다.If the air is blown while the frost has occurred, there is a problem that water is scattered in the indoor unit or discharged into the room from the outlet.
본 발명은 상기와 같은 문제점을 감안하여 이루어진 것으로서, 에어컨에 설치되어 있는 전동 팽창밸브를 적절히 제어하므로서, 예를들면 냉방 모드에서 실내유니트의 열교환기에 건조가 발생하는 것을 방지하는 전동 팽창밸브의 제어방법을 제안하는 것을 목적으로 한다.SUMMARY OF THE INVENTION The present invention has been made in view of the above problems, and by controlling the electric expansion valve installed in an air conditioner appropriately, for example, a control method of an electric expansion valve for preventing drying from occurring in a heat exchanger of an indoor unit in a cooling mode. The purpose is to propose.
도 1은, 본 실시형태에 적용한 에어컨의 냉동사이클을 나타내는 개략구성도.BRIEF DESCRIPTION OF THE DRAWINGS The schematic block diagram which shows the refrigerating cycle of the air conditioner applied to this embodiment.
도 2는, 에어컨의 실내유니트를 나타내는 개략구성도.2 is a schematic configuration diagram showing an indoor unit of an air conditioner.
도 3은, 에어컨의 실내유니트 전기회로의 개략구성을 나타내는 블럭도.3 is a block diagram showing a schematic configuration of an indoor unit electric circuit of an air conditioner.
도 4는, 에어컨의 실외유니트 전기회로의 개략구성을 나타내는 블록도.4 is a block diagram showing a schematic configuration of an outdoor unit electric circuit of an air conditioner.
도 5는, 목표배출온도를 보정하기 위한 보정량 설정의 개략을 나타내는 흐름도.5 is a flowchart showing an outline of a correction amount setting for correcting a target discharge temperature.
도 6은, 목표배출온도 설정의 개략을 나타내는 흐름도.6 is a flowchart showing an outline of setting a target discharge temperature.
도 7은, 실내유니트 열교환기의 건조도에 의거한 콤프레서의 회전수 제한에 대한 한 예를 나타내는 흐름도.7 is a flow chart showing an example of the rotational speed limit of the compressor based on the dryness of the indoor unit heat exchanger.
(도면의 주요부분에 대한 부호의 설명)(Explanation of symbols for the main parts of the drawing)
10. 에어컨 12. 실내유니트10. Air conditioner 12. Indoor unit
14. 실외유니트 18. 열교환기(이용측 열교환기)14. Outdoor unit 18. Heat exchanger (use side heat exchanger)
26. 콤프레서 30. 열교환기(열원측 열교환기)26. Compressor 30. Heat exchanger (heat source side heat exchanger)
36. 전동 팽창밸브 44. 크로스 플로우 팬(cross-flow fan)36. Electric expansion valve 44. Cross-flow fan
74. 마이크로컴퓨터(마이컴으로 약기함)74. Microcomputer (abbreviated as microcomputer)
86. 열교환 온도센서(코일온도 검출수단)86. Heat exchanger temperature sensor (coil temperature detection means)
96. 제어기판, 98. 마이컴96.Control panel, 98.Microcomputer
108. 콤프레서 모터108. Compressor Motor
112. 외기 온도센서(외기온도 검출수단)112. Outside temperature sensor (outside temperature detection means)
150. 냉매 온도센서(배출온도 검출수단)150. Refrigerant temperature sensor (discharge temperature detection means)
152. 냉매 온도센서(흡입온도 검출수단)152. Refrigerant temperature sensor (suction temperature detection means)
본 발명의 공기조화기는, 적어도 콤프레서, 이용측 열교환기, 전동 팽창밸브, 열원측 열교환기를 사용하여 구성되는 냉동사이클 중을 순환하는 냉매의 유량(流量)을 전동 팽창밸브의 개방도를 변경하여 제어하는 공기조화기에 있어서, 콤프레서로부터 토출되는 냉매의 온도가 목표배출온도에 이르도록 전동 팽창밸브의 개방도를 제어함과 동시에, 이용측 열교환기의 온도치, 콤프레서로부터 토출되는 냉매의 온도치, 및 콤프레서에 흡인되는 냉매의 온도치의 몇가지의 값에 의거하여 상기 목표배출온도를 보정하는 것을 특징으로 한다.The air conditioner of the present invention controls the flow rate of the refrigerant circulating in the refrigeration cycle composed of at least a compressor, a use side heat exchanger, an electric expansion valve, and a heat source side heat exchanger by changing the opening degree of the electric expansion valve. In the air conditioner, the opening degree of the electric expansion valve is controlled so that the temperature of the refrigerant discharged from the compressor reaches the target discharge temperature, the temperature value of the heat exchanger on the use side, the temperature value of the refrigerant discharged from the compressor, and The target discharge temperature is corrected based on some values of the temperature values of the refrigerant drawn into the compressor.
본 발명에 의하면, 콤프레서로부터 토출되는 냉매의 온도인 배출온도, 콤프레서에 흡인되는 냉매의 온도인 흡입온도 및 이용측 열교환기의 온도인 코일온도에 의거하여 목표배출온도를 보정한다.According to the present invention, the target discharge temperature is corrected on the basis of the discharge temperature which is the temperature of the refrigerant discharged from the compressor, the suction temperature which is the temperature of the refrigerant sucked into the compressor, and the coil temperature which is the temperature of the use-side heat exchanger.
전동 팽창밸브는, 목표배출온도가 내려가게 되는 것에 의해 열리는 방향으로 조작되며, 이에 의해 열교환기의 온도인 코일온도가 올라가고, 흡입온도는 내려간다.The electric expansion valve is operated in the opening direction by lowering the target discharge temperature, whereby the coil temperature, which is the temperature of the heat exchanger, rises, and the suction temperature falls.
여기에서, 배출온도, 흡입온도 및 코일온도에 의거하여 목표배출온도를 보정하고, 이 목표배출온도에 의거하여 전동 팽창밸브의 개방도를 제어하므로서, 이용측 열교환기의 건조를 억제할 수가 있게 되어, 이용측 열교환기에 건조가 발생하는 것에 의한 크로스 플로우 팬 등으로의 이슬부착을 방지할 수가 있게 된다.Here, the target discharge temperature is corrected based on the discharge temperature, the suction temperature, and the coil temperature, and the opening degree of the electric expansion valve is controlled based on the target discharge temperature, thereby making it possible to suppress drying of the use-side heat exchanger. It is possible to prevent dew adhering to a cross flow fan or the like due to drying occurring in the use-side heat exchanger.
이와 같은 본 발명에서, 상기의 보정은, 코일온도와 흡입온도에 의거하여 연산되는 값이 소정의 값을 초과하였을 때에 목표배출온도를 낮게 보정한다.In the present invention as described above, the above correction corrects the target discharge temperature low when the value calculated based on the coil temperature and the suction temperature exceeds a predetermined value.
열교환기는, 흡입온도가 높아지면 건조가 발생하기 쉬워진다.As the heat exchanger has a high suction temperature, drying is likely to occur.
이로부터, 열교환기에 건조가 발생하기 쉽게 되어 있는지를 코일온도와 배출온도를 비교하여 판단하고, 건조가 발생할 온도로 되어 있을 때에는 목표배출온도가 내려가도록 보정한다.From this, it is judged by comparing the coil temperature and the discharge temperature to determine whether drying is likely to occur in the heat exchanger, and when the drying is to occur, the target discharge temperature is lowered.
이에 의해 열교환기의 건조를 억제할 수가 있게 된다.Thereby, drying of a heat exchanger can be suppressed.
또, 본 발명은, 흡입온도가 코일온도보다 높을 때에, 보정은 전동 팽창밸브가 열리도록 목표배출온도를 보정한다.Further, in the present invention, when the suction temperature is higher than the coil temperature, the correction corrects the target discharge temperature so that the electric expansion valve is opened.
배출온도가 목표배출온도를 초과하면, 이용측 열교환기에 건조가 발생하기 쉽게 된다.When the discharge temperature exceeds the target discharge temperature, drying is likely to occur in the use-side heat exchanger.
여기에서, 배출온도가 높을 때에는 목표배출온도가 내려가도록 보정한다.Here, when the discharge temperature is high, the target discharge temperature is corrected to decrease.
이에 의해, 전동 팽창밸브가 열리는 방향으로 조작되어 배출온도가 내려가고, 코일온도가 약간 올라감과 동시에 흡입온도가 내려가서 열교환기의 건조가 억제된다.As a result, the electric expansion valve is operated in the open direction, the discharge temperature is lowered, the coil temperature is slightly increased, and the suction temperature is lowered, so that drying of the heat exchanger is suppressed.
또한, 본 발명은, 외기온도를 검출하는 외기온도 검출수단을 포함하며, 상기 보정수단은 외기온도에 따라 상기 목표배출온도를 보정하는 것을 특징으로 한다.In addition, the present invention includes an outside air temperature detecting means for detecting the outside air temperature, wherein the correcting means corrects the target discharge temperature according to the outside air temperature.
본 발명에 의하면, 외기온도가 낮아지면 냉매압력도 내려가게 되므로, 외기온도가 낮을 때에는, 외기온도가 높을 때와 비교하여 목표배출온도가 낮게 되도록 보정한다.According to the present invention, when the outside air temperature is lowered, the refrigerant pressure is also lowered. Therefore, when the outside air temperature is low, the target discharge temperature is corrected to be lower than when the outside air temperature is high.
이에 의해, 외기온도가 비교적 낮을 때에 발생하기 쉽게 되는 이용측 열교환기의 건조를 억제할 수가 있다.Thereby, drying of the utilization side heat exchanger which becomes easy to generate | occur | produce when external temperature is comparatively low can be suppressed.
또, 본 발명에서는, 코일온도와 흡입온도에 의거하여 콤프레서의 냉매 토출용량을 제한하는 제한수단을 포함하는 것이 바람직하다.In the present invention, it is preferable to include limiting means for limiting the refrigerant discharge capacity of the compressor based on the coil temperature and the suction temperature.
콤프레서의 회전수를 높이는 것에 의해 냉방능력은 높아진다.By increasing the number of revolutions of the compressor, the cooling capacity is increased.
그러나, 열교환기에 건조가 발생하기 쉬운 상태로 냉방능력을 올리게 되면, 냉매가 액화하여, 열교환기가 더욱 건조하기 쉽게 된다.However, if the cooling capacity is raised in a state where drying is likely to occur in the heat exchanger, the refrigerant liquefies and the heat exchanger is more likely to dry.
이 때문에, 열교환기가 건조하기 쉬운 상태에서는, 냉방능력을 내려가게 하는 것이 좋으나, 적어도 냉방능력이 올라가 버리는 것을 억제하므로서, 열교환기의 건조에 의한 서리부착을 억제할 수가 있다.For this reason, in a state in which the heat exchanger is easy to dry, it is preferable to lower the cooling capacity. However, at least the cooling capacity can be suppressed from rising, so that frost adhesion due to drying of the heat exchanger can be suppressed.
(실시예)(Example)
이하에 본 발명의 실시형태를 설명한다.EMBODIMENT OF THE INVENTION Embodiment of this invention is described below.
도 1에는, 본 실시형태에 적용시킨 공기조화기[이하「에어컨(10)」이라고 함]의 개략구성을 나타내고 있다.1, the schematic structure of the air conditioner (henceforth "air-conditioner 10") applied to this embodiment is shown.
에어컨(10)은, 실내유니트(12)와 실외유니트(14)에 의해 구성되어 있다.The air conditioner 10 is constituted by an indoor unit 12 and an outdoor unit 14.
또한, 실외유니트(14)에는, 복수대의 실내유니트(12)가 접속 가능하게 되어있는 것이라도 좋다.In addition, a plurality of indoor units 12 may be connected to the outdoor unit 14.
에어컨(10)의 실내유니트(12)와 실외유니트(14)는, 가스냉매를 순환시키는 굵은관의 냉매배관(16A)와, 액체냉매를 순환시키는 가는관의 냉매배관(16B)로 접속되어 있다.The indoor unit 12 and the outdoor unit 14 of the air conditioner 10 are connected by a thick pipe refrigerant pipe 16A for circulating a gas refrigerant and a refrigerant pipe 16B for a thin tube circulating a liquid refrigerant. .
실내유니트(12)에는, 이용측 열교환기로서 열교환기(18)이 설치되어 있으며, 냉매배관(16A, 16B)의 각각의 한 끝이, 이 열교환기(18)에 접속되어 있다.The indoor unit 12 is provided with a heat exchanger 18 as a use-side heat exchanger, and one end of each of the refrigerant pipes 16A and 16B is connected to the heat exchanger 18.
또, 냉매배관(16A)의 다른 끝은, 실외유니트(14)의 밸브(20A)에 접속되어 있다.The other end of the refrigerant pipe 16A is connected to the valve 20A of the outdoor unit 14.
이 밸브(20A)는, 머플러(22A)를 통하여 4방밸브(24)에 접속되어 있으며, 이 4방밸브(24)에는, 축압기(accumulator)(28) 및 머플러(22B)가 접속되어 있으며, 이 축압기(28) 및 머플러(22B)의 각각이 콤프레서(26)에 접속되어 있다.The valve 20A is connected to the four-way valve 24 via the muffler 22A, and the accumulator 28 and the muffler 22B are connected to the four-way valve 24. Each of the accumulator 28 and the muffler 22B is connected to the compressor 26.
또한, 실외유니트(14)에는, 열원측 열교환기로서 열교환기(30)이 설치되어 있다.In addition, the outdoor unit 14 is provided with a heat exchanger 30 as a heat source side heat exchanger.
이 열교환기(30)은, 한 쪽이 4방밸브(24)에 접속되어 있으며, 다른쪽이 모세관(32), 여과기(34), 변조기(38)을 통하여 밸브(20B)에 접속되어 있다.One side of the heat exchanger 30 is connected to the four-way valve 24, and the other side of the heat exchanger 30 is connected to the valve 20B through the capillary tube 32, the filter 34, and the modulator 38.
또, 여과기(34)와 변조기(38)의 사이에는, 전동 팽창밸브(36)이 설치되어 있다.In addition, an electric expansion valve 36 is provided between the filter 34 and the modulator 38.
또한, 냉매배관(16B)의 다른 끝은 밸브(20B)에 접속되어 있으며, 이에 의해 실내유니트(12)와 실외유니트(14)의 사이에 냉동사이클을 형성하는 냉매의 밀폐된 순환로가 구성되어 있다.In addition, the other end of the refrigerant pipe 16B is connected to the valve 20B, whereby a closed circulation path of the refrigerant forming a refrigeration cycle is formed between the indoor unit 12 and the outdoor unit 14. .
에어컨(10)은, 콤프레서(26)이 구동되면, 냉동사이클 중을 냉매가 순환된다.In the air conditioner 10, when the compressor 26 is driven, the refrigerant is circulated during the refrigeration cycle.
도 1에서 화살표에 의해 난방운전시(난방모드)와 냉방 또는 제습운전시(냉방모드)의 냉매의 흐름을 나타내는 바와 같이, 에어컨(10)은, 4방밸브(24)의 전환에 의해 운전 모드가 냉방모드(제습모드 포함)와 난방모드로 전환되며, 전동 팽창밸브(36)의 밸브개방도를 제어하므로서, 냉동사이클 중에서의 냉매의 증발온도가 조정된다.As shown by the arrow in FIG. 1, the flow of the refrigerant during heating operation (heating mode) and cooling or dehumidification operation (cooling mode), the air conditioner 10 is changed to the operation mode by switching the four-way valve 24. Is switched to the cooling mode (including the dehumidification mode) and the heating mode, and the evaporation temperature of the refrigerant in the refrigerating cycle is adjusted by controlling the valve opening degree of the electric expansion valve 36.
도 2에 나타내는 바와 같이, 실내유니트(12)는, 흡입구(48)과 배출구(50)이 형성된 케이싱(42)를 구비하고, 이 케이싱(42)의 이면에 설치되어 있는 베이스판(40)에 의해 공기조화를 실시할 실내의 벽면 등에 소정의 높이로 고정된다.As shown in FIG. 2, the indoor unit 12 is provided with the casing 42 in which the inlet 48 and the outlet 50 were formed, and is provided in the base board 40 provided in the back surface of this casing 42. As shown in FIG. It is fixed to a predetermined height on the wall surface of the room where air conditioning is to be performed.
케이싱(42)내에는, 열교환기(18)과 함께 크로스 플로우 팬(44)가 배치되어 있으며, 크로스 플로우 팬(44)의 작동에 의해 실내의 공기가 흡입구(46)으로부터 필터(48)을 통과하여 케이싱(42)내로 흡인된다.In the casing 42, a cross flow fan 44 is disposed together with the heat exchanger 18, and indoor air passes through the filter 48 from the inlet 46 by the operation of the cross flow fan 44. Is sucked into the casing 42.
케이싱(42)내로 흡인된 공기는, 열교환기(18)을 통과한 후, 배출구(50)으로부터 실내로 배출된다.The air sucked into the casing 42 passes through the heat exchanger 18, and then is discharged from the discharge port 50 into the room.
이 공기는, 열교환기(18)을 통과하는 것에 의해 열교환기(18)내를 순환하는 냉매와의 사이에 열교환이 이루어져서, 실내를 공기조화하는 온도가 조절된 공기(공조풍)로 된다.By passing through the heat exchanger 18, this air heat-exchanges with the refrigerant | coolant which circulates in the heat exchanger 18, and becomes air (air-conditioning wind) with the temperature which air-conditions the room.
실내유니트(12)의 배출구(50)에는, 상하 플랩(54)와 좌우 플랩(52)가 설치되어 있으며, 이 좌우 플랩(52)와 상하 플랩(54)에 의해서, 배출구(50)으로부터 배출되는 공조풍의 방향이 변경된다.The upper and lower flaps 54 and the left and right flaps 52 are provided at the discharge port 50 of the indoor unit 12, and are discharged from the discharge port 50 by the left and right flaps 52 and the upper and lower flaps 54. The direction of the air conditioning wind is changed.
에어컨(10)에서는, 좌우 플랩(52)가 수동으로 방향을 바꾸도록 되어 있으며, 주로 상하 플랩(54)의 방향을 제어하므로서 배출구(50)으로부터 불어나오는 공조풍의 풍향을 제어하고 있다.In the air conditioner 10, the left and right flaps 52 change direction manually, and mainly control the direction of the upper and lower flaps 54, and control the wind direction of the air conditioning wind blown from the discharge port 50.
또한, 실내유니트(12)는, 상하 플랩(54)와 함께 좌우 플랩(52)의 방향을 제어하는 것이라도 좋다.In addition, the indoor unit 12 may control the direction of the left and right flaps 52 together with the upper and lower flaps 54.
도 3에 나타내는 바와 같이, 실내유니트(12)에는, 전원기판(56), 제어기판(58) 및 전력계전기(power relay)기판(60)이 설치되어 있다.As shown in FIG. 3, the indoor unit 12 is provided with a power supply board 56, a control board 58, and a power relay board 60.
전원기판(56)에는, 모터전원(62), 제어회로전원(64), 직렬전원(66) 및 구동회로(68)이 설치되어 있으며, 에어컨(10)을 운전하기 위한 전력(예를들면 단상100V의 교류전력)이 공급되도록 되어 있다.The power supply board 56 is provided with a motor power supply 62, a control circuit power supply 64, a series power supply 66, and a drive circuit 68. The power for driving the air conditioner 10 (for example, single phase) is provided. AC power of 100V) is supplied.
또, 제어기판(58)에는, 직렬회로(70), 구동회로(72) 및 마이컴(74)가 설치되어 있다.In addition, the controller board 58 is provided with a series circuit 70, a drive circuit 72, and a microcomputer 74.
전원기판(56)의 구동회로(68)에는, 상기한 크로스 플로우 팬(44)를 구동시키는 팬모터(76)(예를들면 DC브러시레스 모터)이 접속되어 있으며, 제어기판(58)에 설치되어 있는 마이컴(74)로부터의 제어신호에 따라 모터전원(62)로부터 구동전력을 공급한다.A fan motor 76 (for example, a DC brushless motor) for driving the cross flow fan 44 is connected to the drive circuit 68 of the power supply board 56 and installed on the control board 58. The driving power is supplied from the motor power source 62 in accordance with the control signal from the microcomputer 74.
이때, 마이컴(74)는, 구동회로(68)로부터의 출력전압을 12V∼36V의 범위에서 256스탭으로 변화시켜서 제어하고, 실내유니트(12)의 배출구(50)으로부터 배출되는 공조풍의 풍량을 조정한다.At this time, the microcomputer 74 controls by changing the output voltage from the drive circuit 68 to 256 steps in the range of 12V to 36V, and adjusts the air volume of the air conditioning wind discharged from the outlet port 50 of the indoor unit 12. do.
제어기판(58)의 구동회로(72)에는, 전력계전기기판(60) 및 상하 플랩(54)를 조작하는 상하플랩 모터(78)이 접속되어 있다.The upper and lower flap motors 78 for operating the power relay substrate 60 and the upper and lower flaps 54 are connected to the drive circuit 72 of the control board 58.
전력계전기기판(60)에는, 전력계전기(80)과 온도퓨즈 등이 설치되어 있으며, 마이컴(74)로부터의 신호에 의해 전력계전기(80)을 조작하여, 실외유니트(14)로 전력을 공급하기 위하여 접점(80A)를 개폐한다.The power relay substrate 60 is provided with a power relay 80 and a temperature fuse. The power relay 80 is operated by a signal from the microcomputer 74 to supply power to the outdoor unit 14. In order to open and close the contact 80A.
에어컨(10)은, 접점(80A)가 닫혀지는 것에 의해 실외유니트(14)로의 전력의 공급이 가능하게 된다.The air conditioner 10 can supply electric power to the outdoor unit 14 by closing the contact 80A.
또한, 실내유니트(12)와는 별도로 실외유니트(14)로 전력을 공급할 때에는, 후에 설명하는 직렬통신에 의해서 실외유니트(14)의 운전이 제어된다.In addition, when electric power is supplied to the outdoor unit 14 separately from the indoor unit 12, the operation of the outdoor unit 14 is controlled by serial communication described later.
상하플랩 모터(78)은, 마이컴(74)의 제어신호에 따라 작동되어 상하 플랩(54)를 조작한다.The upper and lower flap motor 78 is operated in accordance with the control signal of the microcomputer 74 to operate the upper and lower flaps 54.
이에 의해, 실내유니트(12)의 배출구(50)으로부터 소망하는 영역을 향해 공조풍이 배출된다.As a result, the air-conditioning wind is discharged from the discharge port 50 of the indoor unit 12 toward the desired area.
또, 마이컴(74)에는, 실내온도를 검출하는 실온센서(84) 및 열교환기(18)의 코일온도를 검출하는 열교환 온도센서(86)이 접속되며, 또한, 제어기판(58)에 설치되어 있는 서비스LED 및 운전 전환스위치(88)이 접속되어 있다.In addition, the microcomputer 74 is connected to a room temperature sensor 84 for detecting the room temperature and a heat exchange temperature sensor 86 for detecting the coil temperature of the heat exchanger 18, and is provided on the controller board 58. The service LED and the operation changeover switch 88 are connected.
운전 전환스위치(88)은,「통상운전」과 유지보수시에 행하는「시험운전」의 전환 및, 에어컨(10)의 운전을 정지하는「정지」로 전환된다.The operation switching switch 88 is switched to "normal operation" and "test operation" performed during maintenance, and "stop" to stop the operation of the air conditioner 10.
에어컨(10)은, 운전 전환스위치(88)을「통상운전」으로 설정하여 사용된다.The air conditioner 10 is used by setting the operation switching switch 88 to "normal operation".
이에 의해, 접점(88A)가 닫혀져서, 실내유니트(12)로 운전용 전력이 공급된다.As a result, the contact 88A is closed, and driving electric power is supplied to the indoor unit 12.
또, 운전 전환스위치(88)을「정지」위치로 하므로서, 접점(88A)가 개방되어 실내유니트(12)로의 전력공급이 정지된다.In addition, by setting the operation switching switch 88 to the "stop" position, the contact 88A is opened to stop the power supply to the indoor unit 12.
또한, 서비스LED는, 유지보수시에 점등하므로서, 보수요원에게 자기진단의 결과를 알리도록 되어 있다.In addition, the service LED lights up during maintenance, so that maintenance personnel are notified of the result of the self-diagnosis.
실내유니트(12)에는, 실외유니트(14)로의 배선이 접속되는 단자대(90)이 설치되어 있다.The indoor unit 12 is provided with a terminal block 90 to which wiring to the outdoor unit 14 is connected.
이 단자대(90)의 단자(90A, 90B, 90C)에는, 실내유니트(12)로부터 실외유니트(14)로 공급하는 전원용 배선이 접속가능하도록 되어 있다.Power supply wiring supplied from the indoor unit 12 to the outdoor unit 14 is connectable to the terminals 90A, 90B, 90C of the terminal block 90.
또, 단자(90B, 90C)에는, 실내유니트(12)와 실외유니트(14)의 사이에서 직렬통신을 행하기 위한 배선이 접속된다.Further, wirings for performing serial communication between the indoor unit 12 and the outdoor unit 14 are connected to the terminals 90B and 90C.
마이컴(74) 및 전원회로(56)의 직렬전원(66)에 접속되어 있는 직렬회로(70)은, 단자(90B, 90C)를 통하여 실외유니트(14)로 접속되도록 되어 있으며, 이에 의해 실내유니트(12)와 실외유니트(14)의 사이에서 직렬통신이 가능하도록 되어 있다.The series circuit 70 connected to the microcomputer 74 and the series power supply 66 of the power supply circuit 56 is connected to the outdoor unit 14 through the terminals 90B and 90C. Serial communication is possible between the 12 and the outdoor unit 14.
한편, 마이컴(74)에는, 표시기판(82)가 접속되어 있다.On the other hand, the display substrate 82 is connected to the microcomputer 74.
이 표시기판(82)는, 운전표시용의 표시LED 등이 설치된 표시부와, 도시하지않은 리모콘스위치(120)으로부터 송출되는 조작신호를 수신하는 수광소자를 구비한 수광부가 설치되어 있다.The display substrate 82 is provided with a display unit provided with a display LED for driving display and the like, and a light receiving unit including a light receiving element for receiving an operation signal transmitted from a remote control switch 120 (not shown).
이에 의해, 에어컨(10)에서는, 리모콘스위치가 조작되는 것에 의해 실내유니트(12)와 실외유니트(14)의 사이에서 직류통신을 하면서, 실내가 리모콘스위치에 의해 설정된 공조상태로 되도록 공조운전을 행한다.As a result, in the air conditioner 10, the remote control switch is operated so as to perform direct current communication between the indoor unit 12 and the outdoor unit 14, and perform the air conditioning operation so that the indoor is in the air conditioning state set by the remote control switch. .
도 4에는, 실외유니트(14)의 개략구성을 나타내고 있다.4, the schematic structure of the outdoor unit 14 is shown.
실외유니트(14)에는, 단자대(92)가 설치되며, 이 단자대(92)의 단자(92A, 92B, 92C) 가운데 단자(92B, 92C)에 직렬통신용 배선이 접속된다.The outdoor unit 14 is provided with a terminal block 92, and wiring for serial communication is connected to the terminals 92B and 92C among the terminals 92A, 92B and 92C of the terminal block 92.
또, 실외유니트(14)에는, 단자(90A, 90B)를 통해서 운전전력이 공급된다.In addition, the driving power is supplied to the outdoor unit 14 through the terminals 90A and 90B.
이 실외유니트(14)에는, 정류기판(94), 제어기판(96)이 설치되어 있다.The outdoor unit 14 is provided with a rectifying board 94 and a control board 96.
제어기판(96)에는, 마이컴(98)과 함께, 노이즈필터(100A, 100B, 100C), 직렬회로(102) 및 스위칭전원(104) 등이 설치되어 있다.In addition to the microcomputer 98, the control board 96 is provided with noise filters 100A, 100B, 100C, a series circuit 102, a switching power supply 104, and the like.
정류기판(94)는, 노이즈필터(100A)를 통하여 공급되는 전력을 정류하고, 노이즈필터(100B, 100C)를 통해서 평활화하여 스위칭전원(104)로 출력한다.The rectifying substrate 94 rectifies the power supplied through the noise filter 100A, smoothes it through the noise filters 100B and 100C, and outputs it to the switching power supply 104.
스위칭전원(104)에는, 마이컴(98)과 함께 인버터회로(106)이 접속되어 있으며, 마이컴(98)로부터 출력되는 제어신호에 따른 주파수의 전력을 인버터회로(106)으로부터 콤프레서 모터(108)로 출력하여 콤프레서(26)을 회전구동시키도록 되어 있다.An inverter circuit 106 is connected to the switching power supply 104 together with the microcomputer 98, and the power of the frequency corresponding to the control signal output from the microcomputer 98 is transferred from the inverter circuit 106 to the compressor motor 108. It outputs and rotates the compressor 26. As shown in FIG.
또한, 마이컴(98)은, 인버터회로(106)으로부터 출력되는 전력이, 오프(정지) 또는 14Hz(회전수를 주파수로 환산하여) 이상의 소정의 범위(상한은 운전전류가 소정치를 넘지 않도록 제한된다)가 되도록 제어하고 있으며, 이에 의해 콤프레서 모터(108), 즉 콤프레서(26)의 회전수가 변경되어 콤프레서(26)의 능력[에어컨(10)의 냉방능력]이 제어된다.In addition, the microcomputer 98 limits the power output from the inverter circuit 106 to a predetermined range (upper limit) of not less than (off) or 14 Hz (in terms of rotational frequency), so that the operating current does not exceed a predetermined value. The rotation speed of the compressor motor 108, that is, the compressor 26, is changed, thereby controlling the capacity of the compressor 26 (cooling capacity of the air conditioner 10).
콤프레서(26)의 회전수를 변경하는 방법으로서는, 콤프레서(26)의 구동원에 유도 전동기를 사용할 때에는, PWM이론에 근거하여 주파수의 제어된 의사정현파(疑似正弦波)를 인버터회로(106)으로부터 출력한다.As a method of changing the rotation speed of the compressor 26, when an induction motor is used for the drive source of the compressor 26, the controlled pseudo sine wave of the frequency is output from the inverter circuit 106 based on the PWM theory. do.
의사정현파의 주파수를 변경하므로서 콤프레서(26)의 회전수를 바꿀 수 있다.The rotation speed of the compressor 26 can be changed by changing the frequency of the pseudo sine wave.
또, 콤프레서(26)의 구동원에 직류전동기(직류 브러시레스 모터)를 사용할 때에는, 이 전동기의 회전자의 회전위치에 대응하여 미리 설정된 통전패턴으로 인버터회로(106)을 통해서 소정의 고정자 권선으로 통전을 하여 회전을 유지한다.In addition, when using a direct current motor (DC brushless motor) as a drive source of the compressor 26, it energizes with a predetermined stator winding through the inverter circuit 106 in a predetermined conduction pattern corresponding to the rotational position of the rotor of this motor. To maintain rotation.
이때, 고정자 권선으로의 통전은 소정의 주기로 초핑(chopping)되어 인버터회로(106)을 구성하는 스위칭 소자의 부하를 경감시키고 있다.At this time, energization to the stator windings is chopped at a predetermined cycle to reduce the load on the switching elements constituting the inverter circuit 106.
회전수는 초핑 파형의 ON 듀티를 변경하여 행하여 진다.The rotation speed is performed by changing the ON duty of the chopping waveform.
이 제어기판(96)에는,4방밸브(24) 및 열교환기(30)을 냉각시키기 위한 도시하지 않는 팬을 구동하는 팬 모터(110),팬 모터 콘덴서(110A)가 접속되어 있다.The control board 96 is connected with a fan motor 110 and a fan motor condenser 110A for driving a fan (not shown) for cooling the four-way valve 24 and the heat exchanger 30.
마이컴(98)은,운전 모드에 따라 4방밸브(24)를 전환함과 동시에,실내유니트(12)로부터의 제어신호 및 후술하는 각종 센서의 검출 결과에 의거하여,팬 모터(110)의 ON/OFF 및 콤프레서 모터(108)의 회전수 등을 제어하도록 되어 있다.The microcomputer 98 switches the four-way valve 24 in accordance with the operation mode and turns on the fan motor 110 based on the control signal from the indoor unit 12 and the detection results of various sensors described later. To control the ON / OFF and the rotation speed of the compressor motor 108.
또,마이컴(98)에는,전동 팽창밸브(36)이 접속되어 있다.In addition, a micro expansion valve 36 is connected to the microcomputer 98.
이 전동 팽창밸브(36)에는,도시하지 않은 스테핑(stepping) 모터가 설치되어 있으며,이 스테핑 모터의 구동에 의해 전동 팽창밸브(36)의 개방도가 개폐된다.The stepping motor (not shown) is provided in this electric expansion valve 36, and the opening degree of the electric expansion valve 36 is opened and closed by the drive of this stepping motor.
마이컴(98)은,이 스테핑 모터의 회전량을, 예를들면 0∼512 스탭의 범위로 제어하므로서 전동 팽창밸브(36)의 개방도를 임의로 제어하고 있다.The microcomputer 98 arbitrarily controls the opening degree of the electric expansion valve 36 by controlling the rotation amount of this stepping motor in the range of 0-512 steps, for example.
한편,실외유니트(14)에는,외기온도를 검출하는 외기 온도센서(112),열교환기(30)의 냉매코일의 온도를 검출하는 코일온도 센서(114),콤프레서(26)의 온도를 검출하는 콤프레서온도 센서(116)과 함께,냉동 사이클 중의 냉매 온도를 검출하는 냉매 온도센서(150, 152)가 설치되어 있으며, 이들이 마이컴(98)에 접속되어 있다.On the other hand, the outdoor unit 14 detects the temperature of the ambient temperature sensor 112 for detecting the outside temperature, the coil temperature sensor 114 for detecting the temperature of the refrigerant coil of the heat exchanger 30, and the compressor 26. Along with the compressor temperature sensor 116, refrigerant temperature sensors 150 and 152 for detecting the refrigerant temperature in the refrigeration cycle are provided, and these are connected to the microcomputer 98.
마이컴(98)은 이들 온도센서의 출력을 A/D(아날로그/디지털)변환시킨후 내부에 도입하여 제어에 사용한다.The microcomputer 98 converts the outputs of these temperature sensors to A / D (analog / digital), and then introduces them to the inside for use in the control.
도 1에 나타내는 바와 같이,냉매 온도센서(150)은 콤프레서(26)으로부터의 냉매의 토출측에 설치되어 있으며,콤프레서(26)으로부터 토출되는 냉매의 온도를 배출온도로서 검출하도록 되어 있다.As shown in FIG. 1, the refrigerant temperature sensor 150 is provided on the discharge side of the refrigerant from the compressor 26, and detects the temperature of the refrigerant discharged from the compressor 26 as the discharge temperature.
또,냉매 온도센서(152)는,예를들면 밸브(20A)와 4방밸브(24)의 사이에 설치되어 있으며,에어컨(10)이 냉방 모드로 운전될 때에,콤프레서(26)에 흡인되는 냉매의 온도를 흡입온도로서 검출하도록 되어 있다.In addition, the refrigerant temperature sensor 152 is provided between the valve 20A and the four-way valve 24, for example, and is sucked into the compressor 26 when the air conditioner 10 is operated in the cooling mode. The refrigerant temperature is detected as the suction temperature.
에어컨(10)에서는, 실내 온도 및 설정 온도에 따라 콤프레서(26)의 회전수를 설정하고 콤프레서(26)을 구동한다.In the air conditioner 10, the rotation speed of the compressor 26 is set according to the room temperature and the set temperature, and the compressor 26 is driven.
이 때,실외유니트(14)의 마이컴(98)은,목표배출온도를 설정하여,냉매 온도센서(150)에 의해 검출하는 배출온도가 목표배출온도로 되도록 전동 팽창밸브(36)을 제어한다.At this time, the microcomputer 98 of the outdoor unit 14 sets the target discharge temperature, and controls the electric expansion valve 36 so that the discharge temperature detected by the refrigerant temperature sensor 150 becomes the target discharge temperature.
그런데, 에어컨(10)에서는,냉방 모드로 운전중에 전동 팽창밸브(36)의 개방도를 제어할 때에,실내 유니트(12)의 열교환 온도센서(86)에 의하여 검출하는 코일온도,냉매 온도센서(150)에 의하여 검출하는 배출온도,냉매 온도센서(152)에 의하여 검출하는 흡입온도 및 외기 온도센서(112)에 의하여 검출하는 외기온도에 의거하여 보정한다.By the way, in the air conditioner 10, when controlling the opening degree of the electric expansion valve 36 during operation in the cooling mode, the coil temperature, the refrigerant temperature sensor (detected by the heat exchange temperature sensor 86 of the indoor unit 12) ( Correction is made based on the discharge temperature detected by 150, the suction temperature detected by the refrigerant temperature sensor 152, and the ambient air temperature detected by the outside air temperature sensor 112.
이에 의해,에어컨(10)에서는,실내유니트(12)의 열교환기(18)에 건조가 발생하는 것으로 인한 크로스 플로우 팬(44)의 서리부착,즉,열교환기(18)의 건조를 방지하도록 하고 있다.Accordingly, in the air conditioner 10, the frost of the cross flow fan 44 due to the drying occurring in the heat exchanger 18 of the indoor unit 12, ie, the drying of the heat exchanger 18 is prevented. have.
크로스 플로우 팬(44)의 서리부착은,열교환기(18)의 건조한 곳을 통과한 습기 있는 공기가 냉각된 크로스 플로우 팬에 부딪쳐서 발생한다.Frost attachment of the cross flow fan 44 occurs when the humid air passing through the dry place of the heat exchanger 18 hits the cooled cross flow fan.
에어컨(10)에서는,이 전동 팽창밸브(36)의 개방도의 보정을 목표배출온도를 보정하는 것으로 행하도록 되어 있다.In the air conditioner 10, the opening degree of the electric expansion valve 36 is corrected by correcting the target discharge temperature.
이 때문에,에어컨(10)에서는,전회의 목표배출온도(Tgt-dism),배출온도(T-dis),흡입온도(T-sh) 및 코일온도(T-coil)로부터,실내유니트(12)의 열교환기(18)의 건조도(D-sh)와 함께,전동 팽창밸브(36)의 개방도를 보정할 때의 전동 팽창밸브(36)의 조작도(D-dis)를 구한다.For this reason, in the air conditioner 10, from the last target discharge temperature Tgt-dism, discharge temperature T-dis, suction temperature T-sh, and coil temperature T-coil, the indoor unit 12 is carried out. Together with the dryness degree D-sh of the heat exchanger 18 of the heat exchanger 18, the operation degree D-dis of the electric expansion valve 36 at the time of correcting the opening degree of the electric expansion valve 36 is obtained.
이 건조도(D-sh) 및 조작도(편차)(D-dis)는, 한 예로서 다음과 같이 설정하고 있다.This drying degree (D-sh) and operation degree (deviation) (D-dis) are set as follows as an example.
D-dis = T-dis - Tgt-dismD-dis = T-dis-Tgt-dism
D-sh = T-sh - (T-coil - α)D-sh = T-sh-(T-coil-α)
마이컴(98)에서는, 이 건조도(D-sh) 및 조작도(D-dis)로부터 전동 팽창밸브(36)의 조작량(USH)를 설정하고,이 조작량(USH)로부터 목표배출온도(Tgt-dis)를 보정하기 위한 보정량(CSH)를 설정한다.In the microcomputer 98, the operation amount USH of the electric expansion valve 36 is set from this drying degree D-sh and operation degree D-dis, and the target discharge temperature Tgt- is set from this operation amount USH. Set the correction amount (CSH) to correct dis).
보정량(CSH)는,조작량(USH)와 전회의 보정량(CSHm)으로부터 다음의 식에 의거하여 연산된다.The correction amount CSH is calculated based on the following equation from the operation amount USH and the previous correction amount CSHm.
CSH = USH + CSHmCSH = USH + CSHm
또한,보정량(CSHm)의 초기치는「0」(CSHm=0)으로 하고 있다.In addition, the initial value of the correction amount CSHm is "0" (CSHm = 0).
에어컨(10)에서는, 조작량(USH)를 조작도(D-dis),건조도(D-sh)에 의거하고 있으며, 본 실시형태에서는, 그 한 예로서 표1에 나타내는 바와 같이 설정하여,조작도(D-dis)와 건조도(D-sh)에 따른 조작량(USH)의 설정치를,마이컴(98)에 설치되어 있는 도시하지 않은 메모리에 기억시키고 있다.In the air conditioner 10, the operation amount USH is based on the operation degree D-dis and the drying degree D-sh. In this embodiment, it sets as an example as shown in Table 1, and operates The set value of the manipulated value USH in accordance with the degrees D-dis and D-sh is stored in a memory (not shown) provided in the microcomputer 98.
표 1Table 1
또한,A∼G의 각각의 값은,냉동사이클의 능력에 따라 최적치를 설정하는바,1∼5의 범위가 보다 바람직하다.In addition, each value of A to G sets an optimum value according to the capacity of the refrigeration cycle, and a range of 1 to 5 is more preferable.
한편,목표배출온도(Tgt-dis)는,다음의 식으로 나타내는 바와 같이,전회의 목표배출온도(Tgt-dis)를 외기온도(To) 및 보정량(CSH)에 의해 보정하여 설정하고 있다.On the other hand, the target discharge temperature Tgt-dis is set by correcting the previous target discharge temperature Tgt-dis by the outside air temperature To and the correction amount CSH, as shown by the following equation.
Tgt-dis = Tgt-dis + C(To) + CSHTgt-dis = Tgt-dis + C (To) + CSH
C(To)는 외기온도에 의거한 함수이며 공기조화기의 유니트 마다 조정된다.C (To) is a function based on the outside temperature and is adjusted for each unit of the air conditioner.
즉,에어컨(10)에서는,목표배출온도(Tgt-dis)를 외기온도(To)에 의거하여 시프트(shift)시킴과 동시에,보정량(CSH)를 사용하여 증감시키고 있다.That is, in the air conditioner 10, the target discharge temperature Tgt-dis is shifted based on the outside temperature To, and is increased or decreased using the correction amount CSH.
배출온도(T-dis)가 목표배출온도(Tgt-dism)보다 낮은 경우,조작도(D-dis)는 부(負)가 된다.When the discharge temperature T-dis is lower than the target discharge temperature Tgt-dism, the operation degree D-dis becomes negative.
표 1에 의하여,USH가 내려가는 방향으로 보정되며,전동 팽창밸브(36)은 닫히는 방향으로 조작된다.According to Table 1, USH is corrected in the downward direction, and the electric expansion valve 36 is operated in the closing direction.
또,배출온도(T-dis)가 목표배출온도(Tgt-dism)보다 높고,조작도(D-dis)가 정(正)으로 되면,조작량(USH)가 올라가는 방향으로 보정되며,전동 팽창밸브(36)은 열리는 방향으로 조작된다.When the discharge temperature T-dis is higher than the target discharge temperature Tgt-dism, and the operation degree D-dis is positive, the operation amount USH is corrected in the upward direction. 36 is operated in the opening direction.
또한, 실의 USH는 D-sh의 값에 따라서 다시 보정된다. 흡입온도(T-sh)와 코일온도(T-coil)의 차이인 건조도(D-sh)는,열교환기(18)이 습기가 있을 때에 부(負)로 되고, 열교환기(18)에 건조가 발생하고 있을 때에는 정(正)이 되도록 정수(α)가 설정되어 있다.Also, the actual USH is corrected again according to the value of D-sh. The dryness degree D-sh, which is the difference between the suction temperature T-sh and the coil temperature T-coil, becomes negative when the heat exchanger 18 is wet, and the heat exchanger 18 When drying is occurring, the constant α is set to be positive.
이에 의해,조작량(USH)는,건조도(D-sh)가 정이 되었을 때에 목표배출온도(Tgt-dis)를 내리는 방향으로 보정하도록 설정되며,건조도(D-sh)가 부로 되었을 때에 목표배출온도(Tgt-dis)를 올리는 방향으로 보정하도록 설정되어 있다.Thereby, the operation amount USH is set to correct in the direction of lowering the target discharge temperature Tgt-dis when the dryness D-sh is positive, and the target discharge when the dryness D-sh becomes negative. The temperature Tgt-dis is set to be corrected in the direction of raising.
또한, 본 실시형태에서는, 1D-dis-1,1.0>D-sh-1.0을 불감대로 하여, 난방 모드에서는,보정량(CSH)에 의한 보정을 행하지 않도록 하고 있다(보정량 CSH = 0).In addition, in this embodiment, 1 D-dis -1,1.0 > D-sh With -1.0 as the dead zone, the correction by the correction amount CSH is not performed in the heating mode (correction amount CSH = 0).
C(To)는,외기온도(To)에 따라 미리 정하고 있는 수치이며,본 실시형태에서는, 그 한 예로서 표 2에 나타내는 바와 같이 설정하고 있으며, 이 값이 조작량(USH)와 함께 마이컴(98)의 도시하지 않는 메모리에 기억되고 있다.C (To) is a numerical value previously determined according to the ambient temperature To. In this embodiment, as an example thereof, C (To) is set as shown in Table 2, and this value is set together with the operation amount USH and the microcomputer 98 Is stored in a memory (not shown).
또한, 이 보정 C(To)는 생략해도 좋다.Note that this correction C (To) may be omitted.
표 2TABLE 2
또한, H∼N의 각각의 값은, 냉동사이클의 능력에 따라서 최적치를 설정하는바, 1∼30의 범위가 보다 바람직하다.Moreover, since each value of H-N sets an optimum value according to the capability of a refrigeration cycle, the range of 1-30 is more preferable.
또, 외기온도(To)가 저하하는 방향으로 변화하고 있을 때에는, 외기 온도센서(112)에 의해 검출한 외기온도(To)에 1℃만큼 플러스한 온도를 외기온도(To)로 하여 C(To)를 선택하도록 하고 있다.When the outside air temperature To is changed in a decreasing direction, C (To) is set to the outside air temperature To by adding 1 ° C to the outside air temperature To detected by the outside air temperature sensor 112 as the outside air temperature To. ) To select.
에어컨(10)에서는, 이와 같이 하여 설정한 목표배출온도(Tgt-dis)에 의거하여 전동 팽창밸브(36)[전동 팽창밸브(36)의 스테핑모터]의 제어스탭을 설정하고,설정한 제어스탭으로 전동 팽창밸브(36)을 조작하고 있다.In the air conditioner 10, the control step of the electric expansion valve 36 (stepping motor of the electric expansion valve 36) is set based on the target discharge temperature Tgt-dis set in this way, and the set control step The electric expansion valve 36 is operated.
또한,에어컨(10)에서는,소정시간(ts1) (예를들면 120sec)마다 목표배출온도(Tgt-dis)를 연산하고,PI연산에 의해 배출온도(T-dis)가 목표배출온도(Tgt-dis)로 되도록 소정시간(ts2)(예를들면 10sec)마다 전동 팽창밸브(36)의 스탭 제어를 행하고 있다.Further, in the air conditioner 10, the target discharge temperature Tgt-dis is calculated for each predetermined time ts1 (e.g. 120 sec), and the discharge temperature T-dis is converted to the target discharge temperature Tgt- by the PI operation. Step control of the electric expansion valve 36 is performed every predetermined time ts2 (for example, 10 sec) so as to be dis).
이하에,주로 실외유니트(14)의 마이컴(98)에서 실행되는 전동 팽창밸브(36)을 제어하기 위한 목표배출온도(Tgt-dis)의 보정을 도 5 내지 도 7의 흐름도를 참조하면서 설명한다.The correction of the target discharge temperature Tgt-dis for controlling the electric expansion valve 36 mainly executed by the microcomputer 98 of the outdoor unit 14 will be described below with reference to the flowcharts of FIGS. 5 to 7. .
에어컨(10)에서는,공조운전을 개시하면,목표배출온도(Tgt-dis)를 연산한다.In the air conditioner 10, when the air conditioning operation starts, the target discharge temperature Tgt-dis is calculated.
이 목표배출온도(Tgt-dis)는,예를들면 콤프레서(26)의 회전수(과거의 평균주파수 내지 현재의 회전수) 등에 의거해서 연산하여 설정할 수가 있다.The target discharge temperature Tgt-dis can be calculated and set based on, for example, the rotational speed of the compressor 26 (past average frequency to the current rotational speed).
에어컨(10)에서는,이 목표배출온도(Tgt-dis)를 냉매 온도센서(150)에 의해 검출하는 배출온도(T-dis),냉매 온도센서(152)로 검출하는 흡입온도(T-sh),외기 온도센서(112)로 검출하는 외기온도(To) 및 실내 유니트(12)의 열교환온도 센서(86)에 의해 검출하는 실내유니트(12)의 열교환기(18)의 코일온도(T-coil)에 의거하여 보정하는 것에 의해,전동 팽창밸브(36)의 개방도를 제어하는 목표배출온도(Tgt-dis)를 얻고 있다.In the air conditioner 10, the discharge temperature T-dis detected by the target temperature Tgt-dis by the refrigerant temperature sensor 150, and the suction temperature T-sh detected by the refrigerant temperature sensor 152. , The outside air temperature To detected by the outside temperature sensor 112 and the coil temperature T-coil of the heat exchanger 18 of the indoor unit 12 detected by the heat exchange temperature sensor 86 of the indoor unit 12. ), A target discharge temperature (Tgt-dis) for controlling the opening degree of the electric expansion valve (36) is obtained.
도 5에는,에어컨(10)의 공조운전이 시작되면,소정의 시간(ts1)(예를들면 120sec 간격)로 실행되는 보정량(CSH)의 설정 루틴(routine)을 나타내고 있다.In FIG. 5, when the air conditioning operation of the air conditioner 10 starts, the setting routine routine of the correction amount CSH performed by predetermined time ts1 (for example, 120 sec interval) is shown.
이 흐름도의 최초의 스탭(200)에서는,보정량(CSH)를 클리어(clear) 한 후에, 스탭(202)에서 콤프레서(26)이 정지하고 있는지 아닌지[콤프레서(26)의 회전수(f)가「0」인지 아닌지]를 확인한다.In the first step 200 of this flowchart, after the correction amount CSH is cleared, whether or not the compressor 26 is stopped in the step 202 (the rotation speed f of the compressor 26 is " 0 "or not."
즉,보정량(CSH)의 설정은,콤프레서(26)이 구동을 개시할 때마다 개시된다.That is, the setting of the correction amount CSH is started each time the compressor 26 starts driving.
여기에서,콤프레서(26)이 구동되고 있으면, 스탭(202)에서 긍정 판정되어 스탭(204)로 이행한다.Here, if the compressor 26 is driven, it is affirmatively determined by the staff 202 and the process proceeds to the staff 204.
이 스탭(204)에서는, 조작도(D-dis)의 연산을 행한다.In this step 204, the operation degree D-dis is calculated.
조작도(D-dis)는,배출온도(T-dis)와 전회의 목표배출온도(Tgt-dism)의 온도차로 되어 있으며, 이 스탭(204)에서는,냉매 온도센서(150)에 의해 검출하는 배출온도(T-dis)를 판독하면,이 배출온도(T-dis)와 전회의 목표배출온도(Tgt-dism)와의 차이를 연산한다.The operation degree D-dis is a temperature difference between the discharge temperature T-dis and the previous target discharge temperature Tgt-dism. The step 204 detects by the refrigerant temperature sensor 150. Reading the discharge temperature (T-dis) calculates the difference between this discharge temperature (T-dis) and the previous target discharge temperature (Tgt-dism).
다음의 스탭(206)에서는,연산한 조작도(D-dis)의 절대치가 소정치 이내인지 아닌지를 확인한다.In the next step 206, it is checked whether or not the absolute value of the calculated operation degree D-dis is within a predetermined value.
즉,배출온도(T-dis)와 전회의 목표배출온도(Tgt-dism)의 온도차가 소정의 범위(본 실시형태에서는 그 한 예로서 5℃로 하고 있다)이내로 되었는지 아닌지를 확인한다.That is, it is checked whether or not the temperature difference between the discharge temperature T-dis and the previous target discharge temperature Tgt-dism is within a predetermined range (which is set to 5 ° C as one example in this embodiment).
이에 의해,배출온도(T-dis)와 전회에 설정한 목표배출온도(Tgt-dism)의 온도차가 소정치 범위로 되어 있을 때[스탭(206)에서 긍정 판정],보정치(CSH)의 연산을 행하기 위해, 스탭(208)로 이행한다.As a result, when the temperature difference between the discharge temperature T-dis and the target discharge temperature Tgt-dism set last time is within a predetermined value range (affirmative determination at step 206), calculation of the correction value CSH is performed. In order to do so, the process proceeds to step 208.
이 스탭(208)에서는, 냉매 온도센서(182)에 의해 검출하는 흡입온도(T-sh), 열교환 온도센서(86)에 의해 검출되며 직렬통신에 의하여 실내유니트(12)로부터 송출된 코일온도(T-coil)을 판독하고,열교환기(18)의 건조도(D-sh)를 연산한다.In this step 208, the suction temperature T-sh detected by the refrigerant temperature sensor 182, the coil temperature detected by the heat exchange temperature sensor 86, and sent out from the indoor unit 12 by serial communication ( T-coil) is read and the dryness (D-sh) of the heat exchanger 18 is calculated.
다음에,연산한 조작도(D-dis)와 건조도(D-sh) 및 표 1로부터 조작량(USH)를 설정하고,이 조작량(USH)와 전회의 보정량(CSHm)으로부터 금회의 보정량(CSH)를 산출한다.Next, the operation amount (USH) is set from the calculated operation degree (D-dis) and the drying degree (D-sh) and Table 1, and the current correction amount (CSH) is calculated from the operation amount (USH) and the previous correction amount (CSHm). ) Is calculated.
이와 같이 하여 보정량(CSH)를 구하면,다음의 스탭(210)에서는 연산한 보정량(CSH)가 소정치보다 작은지 아닌지를 확인하며,또,스탭(212)에서는 연산한 보정량(CSH)가 소정치를 초과하고 있는지 아닌지를 확인한다.When the correction amount CSH is obtained in this manner, the next step 210 confirms whether or not the calculated correction amount CSH is smaller than the predetermined value, and in the step 212, the calculated correction amount CSH is the predetermined value. Check if the limit is exceeded.
즉,스탭(210, 212)에서는,연산한 보정량(CSH)가 소정의 범위(본 실시형태에서는 한 예로서,-15<CSH<0)에 있는지 아닌지를 확인한다.That is, the steps 210 and 212 confirm whether or not the calculated correction amount CSH is within a predetermined range (in this embodiment, -15 < CSH < 0).
여기서,연산한 보정량(CSH)가 소정의 범위 이내에 있을 때[스탭(210, 212)에서 긍정판정]에는, 스탭(214)로 이행하여 연산한 보정량(CSH)를 목표배출온도(Tgt-dis)의 연산에 이용하는 보정량으로서 설정한다.Here, when the calculated correction amount CSH is within a predetermined range (positive determination at steps 210 and 212), the correction amount CSH calculated by shifting to the step 214 is calculated as the target discharge temperature Tgt-dis. It is set as the correction amount used for the calculation of.
이에 대하여,연산한 보정량(CSH)가 소정치 이하(CSH-15)로 있을 때에는[스탭(210)에서 부정판정], 스탭(216)으로 이행하여,보정량(CSH)를 하한치에 설정한다(CSH=-15).In contrast, the calculated correction amount CSH is equal to or less than the predetermined value (CSH). -15) (negative determination by the step 210), the process proceeds to the step 216, and sets the correction amount CSH to the lower limit value (CSH = -15).
또,연산한 보정량(CSH)가 소정치 이상(0CSH)으로 있을 때에는[스탭(212)에서 부정판정], 스탭(218)로 이행하여 보정량(CSH)를 상한치로 설정한다(CSH=0).The calculated correction amount CSH is equal to or greater than the predetermined value (0). CSH) (negative determination by the step 212), the process proceeds to the step 218, and the correction amount CSH is set to an upper limit value (CSH = 0).
즉,보정량(CSH)를 소정의 범위(-15CSH0)로 제한하고 있다.That is, the correction amount (CSH) is a predetermined range (-15 CSH Limited to 0).
이와 같이 하여 목표배출온도(Tgt-dis)의 연산에 사용하는 보정량(CSH)를 설정하면,스탭(220)에서는 이 보정량(CSH)를 다음의 보정량(CSH)의 연산에 사용하는 전회의 보정량(CSHm)에 설정한다(CSH=CSHm).When the correction amount CSH used for the calculation of the target discharge temperature Tgt-dis is set in this manner, the step 220 uses the correction amount CSH as the previous correction amount used for the calculation of the next correction amount CSH. CSHm) (CSH = CSHm).
한편,도 6에는,에어컨(10)에서 전동 팽창밸브(36)의 스탭 제어에 이용하는 목표배출온도(Tgt-dis)의 설정의 개략을 나타내고 있으며,최초의 스탭(230)에서는,목표배출온도(Tgt-dis)의 연산을 행한다.6, the outline of setting of the target discharge temperature Tgt-dis used for the step control of the electric expansion valve 36 in the air conditioner 10 is shown. In the first step 230, the target discharge temperature ( Tgt-dis).
다음의 스탭(232)에서는 외기 온도센서(112)에 의하여 검출하고 있는 외기온도(To)를 판독하고,스탭(234)에서는 상기한 표 2로부터 운전 모드와 외기온도(To)에 의거한 보정량 C(To)를 설정한다.The next step 232 reads the outside air temperature To detected by the outside air temperature sensor 112, and the step 234 reads the correction amount C based on the operation mode and the outside air temperature To from Table 2 above. Set (To).
이후,스탭(236)에서는,보정량(CSH)를 사용한 보정을 행할 것인지 아닌지를 확인한다.The staff 236 then checks whether or not correction is performed using the correction amount CSH.
여기에서,보정량(CSH)를 사용한 보정을 행할 때에는,스탭(238)로 이행하고,도 5에 나타내는 흐름도에 의해 설정하고 있는 보정량(CSH)를 판독한 후,스탭(238)에서 외기온도(To)와 보정량(CSH)를 사용한 목표배출온도(Tgt-dis)의 연산,즉 목표배출온도(Tgt-dis)의 보정을 행한다.Here, when performing correction using the correction amount CSH, the process proceeds to the step 238, and after reading the correction amount CSH set by the flowchart shown in FIG. 5, the outside air temperature To is stored in the step 238. ) And calculation of target discharge temperature Tgt-dis using the correction amount CSH, that is, correction of target discharge temperature Tgt-dis.
또한,에어컨(10)에서는,난방 모드시에나 콤프레서(26)의 회전수가 크게 변화 하였을 때 등,미리 목표배출온도(Tgt-dis)의 보정량(CSH)를 사용한 보정을 행하지 않도록 설정되어 있는 조건하에서는,스탭(236)에서 부정판정되어,스탭(240)으로 이행한다.In the air conditioner 10, under the condition that the correction is not performed using the correction amount CSH of the target discharge temperature Tgt-dis, for example, in the heating mode or when the rotation speed of the compressor 26 is greatly changed. It is determined indefinitely by the staff 236, and the process proceeds to the staff 240.
이에 의해,스탭(240)에서는,외기온도(To)에 의거한 보정만을 행하도록 목표배출온도(Tgt-dis)가 연산된다.As a result, the target 240 calculates the target discharge temperature Tgt-dis so as to perform correction only based on the outside temperature To.
이와 같이 하여,목표배출온도(Tgt-dis)를 연산하면,다음의 스탭(242)에서는,목표배출온도(Tgt-dis)가 상한 온도로서 설정하고 있는 소정 온도(예를들면 86℃)이하인지 아닌지를 확인하여,목표배출온도(Tgt-dis)가 상한온도를 초과하고 있지 않을 때[스탭(242)에서 긍정판정]에는 스탭(246)으로 이행하고,이 목표배출온도(Tgt-dis)를 사용하여 전동 팽창밸브(36)의 스탭 제어를 행한다.In this way, when the target discharge temperature Tgt-dis is calculated, the next step 242 is whether the target discharge temperature Tgt-dis is lower than or equal to a predetermined temperature (for example, 86 ° C) set as the upper limit temperature. When the target discharge temperature Tgt-dis has not exceeded the upper limit temperature (affirmative determination at the step 242), the process proceeds to the step 246, and the target discharge temperature Tgt-dis is changed. Step control of the electric expansion valve (36).
또,목표배출온도(Tgt-dis)가,이 상한온도를 초과하고 있을 때[스탭(242)에서 부정판정]에는,목표배출온도(Tgt-dis)를 상한 온도에 설정(예를들면 Tgt-dis=68℃)하고, 이 목표배출온도(Tgt-dis)에 의거하여 전동 팽창밸브(36)의 스탭 제어를 행한다.When the target discharge temperature Tgt-dis exceeds this upper limit temperature (the negative determination by the step 242), the target discharge temperature Tgt-dis is set to the upper limit temperature (for example, Tgt-dis). dis = 68 ° C.), and step control of the electric expansion valve 36 is performed based on this target discharge temperature Tgt-dis.
에어컨(10)이 냉방 모드로 운전하고 있을 때에, 흡입온도(T-sh)와 실내유니트(16)의 열교환기(18)의 온도인 코일온도(T-coil)로부터,열교환기(18)에 건조가 발생하기 어려운 상태,즉,열교환기(18)이 출구까지 습기가 있는 상태에서는 건조도(D-sh)가 부(負)로 되어 있다.When the air conditioner 10 is operating in the cooling mode, from the coil temperature T-coil, which is the temperature of the heat exchanger 18 of the suction temperature T-sh and the indoor unit 16, to the heat exchanger 18; In a state in which drying is unlikely to occur, that is, in a state in which the heat exchanger 18 is wet to the outlet, the dryness degree D-sh is negative.
이에 대하여,코일온도(T-coil)이 상승하면,열교환기(18)의 출구 부근에 건조가 생기기 쉽게 된다.In contrast, when the coil temperature T-coil rises, drying tends to occur near the outlet of the heat exchanger 18.
열교환기(18)에 건조가 발생하면,크로스 플로우 팬(44)에 이슬부착이 발생한다.When drying occurs in the heat exchanger 18, dew adhesion occurs in the cross flow fan 44.
이 때,흡입온도(T-sh)에 대하여 코일온도(T-coil)이 상대적으로 상승하게 되어,건조도(D-sh)도 커진다.At this time, the coil temperature (T-coil) increases relative to the suction temperature (T-sh), and the dryness (D-sh) also increases.
한편,배출온도(T-dis)가 목표배출온도(Tgt-dis)보다 높을 때에는 조작도(D-dis)는 정(正)의 값이 되며,배출온도(T-dis)가 목표배출온도(Tgt-dis)보다 낮을 때에는 조작도(D-dis)는 부(負)의 값으로 된다.On the other hand, when the discharge temperature T-dis is higher than the target discharge temperature Tgt-dis, the operation degree D-dis becomes a positive value, and the discharge temperature T-dis is the target discharge temperature (T-dis). When it is lower than Tgt-dis, the operation degree D-dis becomes a negative value.
또,배출온도(T-dis)는,콤프레서(26)의 회전수가 일정하면,전동 팽창밸브(36)을 열어서 냉매 유량을 증가시키게 하여 내리게 할 수가 있으며, 전동 팽창밸브(36)의 개방도를 좁혀서 냉매의 유량을 억제하는 것에 의해 올리게 할 수가 있다.Moreover, when the rotation speed of the compressor 26 is constant, the discharge temperature T-dis can be lowered by opening the electric expansion valve 36 to increase the flow rate of the refrigerant, thereby reducing the opening degree of the electric expansion valve 36. It can be made narrow by raising the flow volume of refrigerant | coolant.
목표배출온도(Tgt-dis)는,보정량(CSH)를 크게 하므로서 높아지고, 보정량(CSH)를 작게 하므로서 내려간다.The target discharge temperature Tgt-dis is increased by increasing the correction amount CSH and decreases by decreasing the correction amount CSH.
보정량(CSH)의 조작량(USH)는,건조도(D-sh)가 높아지므로서,보정량(CSH)를 감소시키는 방향으로 설정된다.The operation amount USH of the correction amount CSH is set in the direction of decreasing the correction amount CSH as the dryness D-sh increases.
이에 의해,열교환기(18)이 습기가 있기 쉬운 상태로 되어,건조도(D-sh)가 높아지면,목표배출온도(Tgt-dis)가 올려져서,전동 팽창밸브(36)이 열리는 방향으로 조작된다.As a result, the heat exchanger 18 is in a state in which moisture is likely to be wet, and when the dryness D-sh becomes high, the target discharge temperature Tgt-dis is raised to the direction in which the electric expansion valve 36 opens. Manipulated.
따라서, 열교환기(18)의 건조가 억제된다.Therefore, drying of the heat exchanger 18 is suppressed.
한편,냉매 압력은,외기온도(To)의 영향을 적지않게 받는다.On the other hand, the refrigerant pressure is quite affected by the outside temperature (To).
즉,외기온도가 높아지면 냉매 압력도 상승하고,외기온도가 낮아지면 냉매 압력도 저하한다.In other words, when the outside temperature increases, the refrigerant pressure increases, and when the outside temperature decreases, the refrigerant pressure also decreases.
이 때문에,전동 팽창밸브(36)의 개방도가 동일하여도,외기온도(To)가 낮으면 실외의 열교환기(30)에 냉매가 쌓이기 쉬워지고,그 결과 열교환기(18)에 공급되는 냉매가 감소되어 열교환기(18)에 건조가 생기기 쉽게 된다.For this reason, even if the opening degree of the electric expansion valve 36 is the same, when the outdoor temperature To is low, the refrigerant tends to accumulate in the outdoor heat exchanger 30, and as a result, the refrigerant supplied to the heat exchanger 18. Is reduced, so that drying occurs easily in the heat exchanger (18).
이에 대하여,본 발명에서는,외기온도(To)가 높을 때에,목표배출온도(Tgt-dis)가 높아지도록 시프트 시키고 있다.In contrast, in the present invention, when the outside temperature To is high, the target discharge temperature Tgt-dis is shifted to be high.
이에 의해,외기온도(To)가 낮을 때에 전동 팽창밸브(36)이 필요 이상으로 열리는 일이 없으며, 동시에 외기온도(To)가 높을 때에 열교환기(18)에 건조가 발생하는 것을 억제할 수가 있다.Thereby, the electric expansion valve 36 does not open more than necessary when the outdoor air temperature To is low, and at the same time, it is possible to suppress the drying of the heat exchanger 18 when the outdoor air temperature To is high. .
한편,에어컨(10)에서는,건조도(D-sh)에 의거하여 콤프레서(26)의 회전수 제한을 행하고 있다.On the other hand, in the air conditioner 10, the rotation speed of the compressor 26 is limited based on the dryness degree D-sh.
도 7에는,목표배출온도(Tgt-dis)의 보정에 사용하는 건조도(D-sh)에 의거한 콤프레서(26)의 회전수 제한의 한 예를 나타내고 있다.FIG. 7 shows an example of the rotational speed limitation of the compressor 26 based on the dryness level D-sh used to correct the target discharge temperature Tgt-dis.
이 흐름도에서는, 최초의 스탭(250)에서,이 흐름도 중에서 사용하는 타이머나 플래그(flag)의 초기설정(reset)을 행한 후에,스탭(252)에서 도 5에 나타내는 흐름도에서 연산하고 있는 건조도(D-sh)를 판독한다.In this flowchart, after the initial setting of the timer or flag used in this flowchart is performed in the first step 250, the step 252 calculates the dryness degree calculated in the flowchart shown in FIG. D-sh).
다음 스탭(254)에서는,이 건조도(D-sh)가 소정치(한 예로서 3.0)를 초과하고 있는지 아닌지를 확인하고,또,스탭(256)에서 전동 팽창밸브(36)의 제어스탭을 판독하고,스탭(258)에서 제어 스탭이 상한에 이르고 있는지 아닌지를 확인한다.In the next step 254, it is checked whether or not the dryness level D-sh exceeds a predetermined value (3.0 as an example), and the control step of the electric expansion valve 36 is removed from the step 256. It reads and checks in step 258 whether the control step reaches the upper limit.
여기에서,건조도(D-sh)가 소정치 미만(D-sh<3.0) 또는,전동 팽창밸브(36)의 제어 스탭이 상한에 이르고 있지 않을 때[스탭(254) 또는 스탭(258)에서 부정 판정]에는 스탭(260)으로 이행하고,콤프레서(26)의 회전수로부터 콤프레서(26)이 정지 상태인지 아닌지를 확인하여,콤프레서(26)이 정지 상태가 되면[스탭(260)에서 부정 판정],이 흐름도를 일단 종료한다.Here, when dryness degree D-sh is less than predetermined value (D-sh <3.0), or when the control staff of the electric expansion valve 36 does not reach the upper limit (in the step 254 or the step 258). Negative determination], the process proceeds to the step 260 and checks whether the compressor 26 is in a stopped state from the rotational speed of the compressor 26, and when the compressor 26 is in a stopped state (negative determination in the step 260). ], Complete this flowchart once.
즉,이 흐름도는,콤프레서(26)의 운전중에만 실행되며,콤프레서(26)이 정지 상태가 될 때마다 리셋(reset)된다.That is, this flowchart is executed only during the operation of the compressor 26, and is reset every time the compressor 26 is stopped.
한편,건조도(D-sh)가 소정치(D-sh3.0)를 초과하고,또한 전동 팽창밸브(36)의 제어 스탭이 상한에 이르면[스탭(254) 및 스탭(258)에서 긍정 판정],스탭(262)로 이행하여 콤프레서(26)의 회전수를 제한하기 위한 타이머를 리셋/스타트 시킨다.On the other hand, the dryness (D-sh) is a predetermined value (D-sh 3.0), and when the control staff of the electric expansion valve 36 reaches an upper limit (affirmative determination in the staff 254 and the staff 258), the process shifts to the staff 262 and the rotation speed of the compressor 26 is increased. Reset / start the timer to limit.
이후,스탭(264, 266, 268, 270)에서는,스탭(252, 254, 256, 258)과 마찬가지로,건조도(D-sh)가 소정치 이상으로 되어 있는지의 여부 및 전동 팽창밸브(36)의 제어 스탭이 상한에 이르고 있는지의 여부를 확인한다.Thereafter, in the steps 264, 266, 268, and 270, as in the steps 252, 254, 256, and 258, whether the dryness degree D-sh is equal to or greater than a predetermined value and the electric expansion valve 36 Check whether the control staff has reached the upper limit.
또, 스탭(272)에서는,타이머에 의해 계측하고 있는 시간이 소정의 시간(예를들면 30min)에 이르렀는지 아닌지를 확인한다.In addition, the staff 272 checks whether or not the time measured by the timer has reached a predetermined time (for example, 30 minutes).
즉,스탭(264)∼(272)에서는,건조도(D-sh)가 소정치 이상이면서 전동 팽창밸브(26)의 제어 스탭이 상한에 이르고 있는 상태가 소정 시간 계속되고 있는지 여부를 확인한다.That is, in the steps 264 to 272, it is checked whether the state where the control step of the electric expansion valve 26 reaches the upper limit while the dryness D-sh is greater than or equal to the predetermined value continues for a predetermined time.
이에 의해,소정 시간내에 건조도(D-sh)와 제어 스탭의 어느 한쪽이 내려가면[스탭(272)에서 부정 판정되고 있는 상태에서 스탭(266) 또는 스탭(270)에서 부정 판정],콤프레서(26)의 회전수의 제한을 행하지 않고 스탭(252)에 되돌아 온다.Thus, if either of the dryness level D-sh and the control staff falls within a predetermined time (negative determination by the staff 266 or the staff 270 in the state of being negatively determined by the staff 272), the compressor ( It returns to the step 252 without restricting the rotation speed of 26).
이에 대하여,건조도(D-sh)가 소정치 이상이면서 전동 팽창밸브(26)의 제어 스탭이 상한에 이르고 있는 상태가 소정시간 계속되면[스탭(266, 270, 272)에서 긍정판정],콤프레서(26)의 회전수의 제한을 행한다.On the other hand, if the dryness degree D-sh is more than a predetermined value and the state in which the control staff of the electric expansion valve 26 reaches the upper limit continues for a predetermined time (affirmative determination in the steps 266, 270 and 272), the compressor The rotation speed of (26) is limited.
이 콤프레서(26)의 회전수의 제한은,스탭(274)에서 콤프레서(26)의 회전수를 소정치(예를들면 현재 회전수의 75%)까지 다운시키고,또한 스탭(276)에서 회전수의 상승을 금지시킨다.Restriction of the rotation speed of the compressor 26 lowers the rotation speed of the compressor 26 at the step 274 to a predetermined value (for example, 75% of the current rotation speed), and the rotation speed at the step 276. Prohibit the rise of.
이에 의해,에어컨(10)에서는,콤프레서(26)의 회전수를 내리게 함과 동시에,회전수의 상승,즉,냉매의 토출압의 상승이 금지된다.As a result, in the air conditioner 10, the rotation speed of the compressor 26 is lowered, and the increase in the rotation speed, that is, the increase in the discharge pressure of the refrigerant is prohibited.
이에 의해,콤프레서(26)의 회전수와 함께 냉매의 토출압도 저하되어,예를들면,냉동 사이클중,특히 실외유니트의 열교환기(30)에 액화된 냉매가 체류하여,실내유니트(12)의 열교환기(18)에 건조가 생기기 쉬운 상태로 되어 있어도,열교환기(18)의 건조를 억제하고,크로스 플로우 팬(44)에 서리의 부착이 생기는 것을 방지할 수 있다.As a result, the discharge pressure of the refrigerant decreases with the rotation speed of the compressor 26. For example, during the freezing cycle, the liquefied refrigerant stays in the heat exchanger 30 of the outdoor unit. Even if the heat exchanger 18 is in a state where drying is likely to occur, drying of the heat exchanger 18 can be suppressed and frost can be prevented from occurring in the cross flow fan 44.
다음 스탭(278)에서는,플래그(flag)가 세트되어 있는지 아닌지를 확인하여,플래그가 리셋되어 있을 때에는,스탭(280)로 이행하여 회전수의 상승 금지가 설정된 것을 나타내는 플래그를 세트한다.In the next step 278, it is checked whether or not a flag is set, and when the flag is reset, the process shifts to the step 280 to set a flag indicating that the increase in the rotation speed is set.
이렇게 하여 콤프레서(26)의 회전수에 제한을 가하면,다음의 스탭(282)에서는 건조도(D-sh)를 판독하고,이 건조도(D-sh)가 소정의 값(예를들면 -1. 0) 이하로 내려갔는지 아닌지를 확인한다.In this way, if the rotation speed of the compressor 26 is limited, the next staff 282 reads the dryness level D-sh, and the dryness level D-sh is a predetermined value (e.g. -1 0) Check if it goes down below.
여기에서,건조도(D-sh)가 소정의 값 미만까지 내려가서,열교환기(18)이 습기 있는 상태로 되면,스탭(284)에서 긍정 판정된다.Here, when the dryness degree D-sh falls below a predetermined value and the heat exchanger 18 is in a wet state, it is affirmatively determined by the staff 284.
이에 의해,스탭(286)으로 이행하여,콤프레서(26)의 회전수의 상승을 해제한다.As a result, the process proceeds to the step 286 and releases the increase in the rotation speed of the compressor 26.
이와 같이,에어컨(10)에서는,목표배출온도(Tgt-dis)를 보정하는 것에 의해 실내유니트(12)의 열교환기(18)에 건조가 발생하는 것을 방지하고 있지만,그래도 열교환기(18)에 건조가 발생하는 상태가 계속되고 있을 때에는,콤프레서(26)의 회전수를 내리게 함과 동시에,콤프레서(26)의 회전수의 상승을 금지하므로서,보다 확실하게 열교환기(18)의 건조를 방지하고 있다.As described above, the air conditioner 10 prevents drying from occurring in the heat exchanger 18 of the indoor unit 12 by correcting the target discharge temperature Tgt-dis. When the drying is being continued, the rotation speed of the compressor 26 is lowered, and the increase in the rotation speed of the compressor 26 is prohibited, thereby preventing the drying of the heat exchanger 18 more reliably. have.
또,열교환기(18)에 건조가 생기지 않는 상태에 이르면,콤프레서(26)의 회전수의 상승금지를 해제한다.When the heat exchanger 18 reaches a state where no drying occurs, the prohibition of the increase in the rotation speed of the compressor 26 is released.
한편,콤프레서(26)의 회전수의 상승금지가 설정되고 플래그가 이미 세트되어 있을 때에는,스탭(278)에서 긍정판정되고 스탭(288)로 이행하여,콤프레서(26)이 정지 상태로 되었는지 아닌지를 확인한다.On the other hand, when the prohibition of the increase in the rotation speed of the compressor 26 is set and the flag is already set, affirmative determination is made by the staff 278, the process proceeds to the staff 288, and whether or not the compressor 26 is in a stopped state. Check it.
이에 의해,콤프레서(26)이 정지상태로 되면,스탭(290)으로 이행하여 콤프레서(26)의 회전수의 상승금지를 해제한 후에,이 흐름도를 일단 종료한다.As a result, when the compressor 26 is in the stopped state, the flow proceeds to the step 290 to release the prohibition of the increase in the rotation speed of the compressor 26, and then the flowchart is finished once.
이와 같이,에어컨(10)에서는, 열교환기(18)의 건조를 방지하기 위해 콤프레서(26)의 회전수의 제한이 2회째가 되면,콤프레서(26)이 정지할 때까지 회전수의 상승금지를 해제하지 않도록 하고 있다.Thus, in the air conditioner 10, when the rotation speed of the compressor 26 reaches the 2nd time in order to prevent drying of the heat exchanger 18, the increase of the rotation speed is prohibited until the compressor 26 stops. Do not release it.
또한,이상 설명한 본 실시형태에 적용한 에어컨(10)에서는,본 발명이 적용되는 공기조화기의 구성을 한정하는 것이 아니다.In addition, in the air conditioner 10 applied to this embodiment demonstrated above, the structure of the air conditioner to which this invention is applied is not limited.
본 발명은, 전동 팽창밸브에 의해 냉동 사이클 중의 냉매의 유량을 조정하는 임의의 구성의 공기조화기에 적용할 수가 있다.The present invention can be applied to an air conditioner of any configuration in which the flow rate of the refrigerant in the refrigeration cycle is adjusted by the electric expansion valve.
이상 설명한 바와 같이 본 발명에 의하면, 배출온도, 흡입온도, 코일온도에 의거하여 목표배출온도를 보정하므로서, 실내유니트의 열교환기의 건조에 대응하여 전동 팽창밸브를 제어할 수가 있으며, 열교환기의 건조로 인한 서리의 부착을 방지할 수 있다는 뛰어난 효과가 얻어진다.As described above, according to the present invention, by adjusting the target discharge temperature based on the discharge temperature, the suction temperature, and the coil temperature, the electric expansion valve can be controlled in response to the drying of the heat exchanger of the indoor unit. An excellent effect can be obtained that can prevent the adhesion of frost due to.
Claims (5)
Applications Claiming Priority (2)
Application Number | Priority Date | Filing Date | Title |
---|---|---|---|
JP2632599 | 1999-02-03 | ||
JP11-026325 | 1999-02-03 |
Publications (2)
Publication Number | Publication Date |
---|---|
KR20000057057A true KR20000057057A (en) | 2000-09-15 |
KR100545009B1 KR100545009B1 (en) | 2006-01-24 |
Family
ID=12190270
Family Applications (1)
Application Number | Title | Priority Date | Filing Date |
---|---|---|---|
KR1019990057616A KR100545009B1 (en) | 1999-02-03 | 1999-12-14 | Air-conditioner |
Country Status (2)
Country | Link |
---|---|
KR (1) | KR100545009B1 (en) |
CN (1) | CN1124460C (en) |
Cited By (2)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
WO2004068045A1 (en) * | 2003-01-28 | 2004-08-12 | Halla Climate Control Corp. | Supercritical refrigerating cycle |
CN108626844A (en) * | 2018-04-18 | 2018-10-09 | 芜湖乐锐思信息咨询有限公司 | The application method of heating ventilation air-conditioning system based on big data technology |
Families Citing this family (8)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
JP3772777B2 (en) * | 2002-03-27 | 2006-05-10 | ダイキン工業株式会社 | Air conditioner and control method of air conditioner |
KR101479240B1 (en) * | 2008-07-14 | 2015-01-06 | 삼성전자 주식회사 | Air conditioner and method of controlling the same |
JP5040975B2 (en) * | 2008-09-30 | 2012-10-03 | ダイキン工業株式会社 | Leakage diagnostic device |
CN104005214B (en) * | 2013-02-22 | 2017-09-29 | 青岛海尔洗衣机有限公司 | A kind of control method of heat pump clothes dryer expansion valve |
CN103398446B (en) * | 2013-07-11 | 2015-09-30 | 四川长虹电器股份有限公司 | A kind of method improving air-conditioning heating refrigeration |
CN105627524B (en) * | 2016-03-14 | 2018-06-01 | 广东美的制冷设备有限公司 | Air conditioner anti-freeze control method and air conditioner |
CN109099559A (en) * | 2018-07-25 | 2018-12-28 | 广东美的制冷设备有限公司 | The modification method and device of air conditioner delivery temperature |
CN111322801B (en) * | 2020-02-27 | 2021-05-11 | 广东志高暖通设备股份有限公司 | Control method and device of electronic expansion valve |
-
1999
- 1999-12-14 KR KR1019990057616A patent/KR100545009B1/en not_active IP Right Cessation
-
2000
- 2000-01-28 CN CN00101669A patent/CN1124460C/en not_active Expired - Fee Related
Cited By (2)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
WO2004068045A1 (en) * | 2003-01-28 | 2004-08-12 | Halla Climate Control Corp. | Supercritical refrigerating cycle |
CN108626844A (en) * | 2018-04-18 | 2018-10-09 | 芜湖乐锐思信息咨询有限公司 | The application method of heating ventilation air-conditioning system based on big data technology |
Also Published As
Publication number | Publication date |
---|---|
CN1124460C (en) | 2003-10-15 |
CN1264024A (en) | 2000-08-23 |
KR100545009B1 (en) | 2006-01-24 |
Similar Documents
Publication | Publication Date | Title |
---|---|---|
KR960010637B1 (en) | Control device for an air-conditioner | |
EP0947783A2 (en) | Air conditioner | |
KR100545009B1 (en) | Air-conditioner | |
JPH10339500A (en) | Air conditioner | |
JPH11218350A (en) | Air conditioner | |
JP4259668B2 (en) | Air conditioner | |
KR100210086B1 (en) | Defrost operating change device and method of airconditioner | |
JP2007212080A (en) | Air conditioner | |
JP2000292013A (en) | Air-conditioner | |
JP4183320B2 (en) | Air conditioner | |
KR100561943B1 (en) | Control method for electro-drive expansion valve | |
KR101153421B1 (en) | Condensation volume control method for air conditioner | |
JP4259696B2 (en) | Air conditioner test run judgment method | |
JP4201416B2 (en) | Air conditioner | |
JP3762495B2 (en) | Air conditioner | |
JP4236347B2 (en) | Air conditioner | |
JP4242979B2 (en) | Air conditioner | |
JP4190099B2 (en) | Control method of air conditioner | |
JP4404420B2 (en) | Air conditioner control device | |
JP2001254985A (en) | Air conditioner | |
JP4510964B2 (en) | Air conditioner control device | |
KR20010056393A (en) | Dehumidifying operation control method for air conditioner | |
JP2002257382A (en) | Air conditioner | |
JP2001065947A (en) | Control method of air conditioner | |
JPH09250797A (en) | Air conditioner |
Legal Events
Date | Code | Title | Description |
---|---|---|---|
A201 | Request for examination | ||
E902 | Notification of reason for refusal | ||
E701 | Decision to grant or registration of patent right | ||
GRNT | Written decision to grant | ||
FPAY | Annual fee payment |
Payment date: 20111216 Year of fee payment: 7 |
|
FPAY | Annual fee payment |
Payment date: 20121221 Year of fee payment: 8 |
|
LAPS | Lapse due to unpaid annual fee |