Detailed Description
The grid requires that a wind power plant which is operated in a networking mode must have fault ride-through capability, and when the voltage drops to 20% of rated voltage due to grid side fault, the wind power plant must be operated in a non-networking mode within 625ms, and normal operation can be rapidly recovered after transient fault is eliminated. The invention provides a fault ride-through control method for a wind power plant through VSC-HVDC grid connection, a voltage source converter-based flexible direct current transmission system (VSC-HVDC) is widely applied by the advantages of independent, flexible and controllable active power and reactive power, no need of phase-change voltage of a power grid and the like, the permeability of the flexible direct current transmission system in the power grid is continuously improved, and the wind power plant through high-voltage direct current transmission grid connection has the fault ride-through capability for ensuring safe operation of the power grid. Aiming at the defects of the traditional fault ride-through method based on direct-current energy consumption resistance, an improved modularized energy consumption circuit is designed, and a coordination control strategy of a wind turbine generator is designed based on the modularized energy consumption circuit to realize the fault ride-through control method of a wind power plant through VSC-HVDC grid connection.
As shown in fig. 1, a method for controlling a wind farm to ride through a VSC-HVDC grid connection fault includes the following steps:
the method comprises the following steps of firstly, describing a topological structure and a working principle of the VSC, establishing a mathematical model of the VSC, and analyzing the operating characteristics of a system when a power grid fails;
designing a topological structure of the modularized energy consumption resistor in the VSC-HVDC system;
and thirdly, combining a wind turbine generator design coordination control method on the basis of the modularized energy consumption resistor to realize fault ride through.
Furthermore, in the first step, because the double-fed wind turbine generator is connected with the power grid through the flexible direct-current transmission system, and the wind turbine realizes decoupling control with the power grid through the direct-current transmission line, when the power grid side fails, a corresponding control strategy can be adopted on a converter part between the direct-current line and the power grid side. The mathematical model of the grid-side converter under the dq synchronous rotation coordinate system is as follows:
in the formula (1), the grid side current is used as the current of the converterThe flow direction is positive direction, UsdAnd UsqD-axis and q-axis components of the grid voltage connected to the grid side respectively; u shapegdAnd UgqOutputting d-axis and q-axis components of the alternating voltage for the grid-side converter; i.e. isdAnd isqD-axis and q-axis components of the net side current, respectively; omega is the fundamental angular frequency of the power grid; r and L are respectively an alternating current side circuit resistor and a filter inductor.
Therefore, according to the mathematical model of the grid-side converter under the dq two-phase synchronous rotating coordinate system, equivalent circuits of a d-axis and q-axis alternating current system and a direct current link of the grid-side converter can be obtained, as shown in fig. 2(a), (b) and (c).
If losses in the network side converter and the reactor are neglected, it can be seen from fig. 2 that active power P injected into the grid through the network side converterinvCan be expressed as:
with grid voltage oriented on the d-axis, there is UsqWhen 0, formula (2) can be rewritten as:
and the output active power P of the wind field side converterrecComprises the following steps:
Prec=Udcirec (4)
during normal operation, direct current voltage keeps invariable, and according to the power balance principle, the power of direct current bus both sides equals, promptly:
the energy Δ P flowing through the dc-side capacitor can then be expressed as:
in a steady state, the power of the inverters on both sides is equal, so that Δ P is equal to 0, the dc voltage is constant at the reference value, and no current passes through the capacitor.
When the power grid is in fault, under the condition that the current limitation of the converter is not considered in an ideal state, the power grid voltage is limited by UsdInstantly falls to U'sdBecause the wind turbine generator and the power grid are basically isolated through the grid-connected converter system, the active power output by the wind field side converter is basically kept constant, and the d-axis current of the grid side converter also needs to be i in order to maintain the active power balance of the two side converterssdIs increased to i'sdNamely, the following steps are provided:
in actual operation, the grid-side converter has certain current limiting measures, the passing current is not allowed to increase infinitely, the current limiting effect of a limiter is considered, and the actual instantaneous d-axis current at the moment is set as i″sdAnd i ″)sd<i′sdThen, there are:
Prec=P′inv+ΔP (9)
p 'in the formula (8)'invThe actual active power of the network side is obtained when the voltage of the power grid drops.
From the above analysis, it can be known that the grid voltage drop causes PinvThe direct-current bus voltage U is greatly reduced, the active power output by the wind turbine generator is basically kept stable, the active deviation delta P of two sides of a direct-current link is larger than zero, namely, the energy generated by the double-fed wind turbine generator cannot be completely input into a power grid, redundant unbalanced energy is injected into a middle direct-current bus, and the direct-current bus voltage U is directly caused by charging a capacitordcRises rapidly. If effective measures are not taken in time, the large fluctuation of the direct current voltage can cause the direct current bus capacitor and the full capacitorDamage to the power converter device. Therefore, the doubly-fed wind power system and the whole power grid cannot be guaranteed to operate safely and stably based on the conventional control strategies of the power grid side and the grid side under the ideal steady-state working condition of the power grid, and the control strategy of the current conversion system needs to be further optimally designed.
And further, in the second step, energy consumption resistors are put between the direct current side converter station and the power grid side converter station, the modular energy consumption resistors are designed according to the idea of the modular converter, and the topological structure of the energy consumption resistors is designed.
From the above analysis, it can be seen that when a fault occurs at the PCC of the receiving-end power grid and causes a voltage drop, the fault ride-through operation of the system can be ensured by eliminating the difference power between the dc side and the power grid side, so that a controllable energy consumption resistor R can be put between the dc side and the power grid side converter stationchTo absorb the differential power during the fault, as shown in fig. 3, to maintain the stability of the dc voltage during the fault, and ensure the fault-ride-through operation of the system. The resistor capacity and the occupied area required by adopting a single energy consumption resistor to absorb the differential power are large, and higher requirements are put on the heat dissipation of the system.
Aiming at the defects, a dissipative resistor R is providedchSplit into n resistors R with same resistancenAre connected in parallel, each individual resistor RnCan be independently put in and cut off, the topological structure is shown in figure 4, and a series of sub-modules (SM) are connected in parallel to form a modular energy consumption circuit. Each sub-module consumes power when independently turned on
Wherein, UdcAnd the rated voltage of the direct current side is represented, and even if the alternating current network side has serious faults to drop the voltage of a PCC point to 0, the GSVSC cannot transmit power, and the wind power plant still normally transmits power.
If n submodules are in total, when all the submodules are opened, the power difference when the most serious fault occurs on the power grid side, namely the sum of the direct current system, is completely consumedConstant active power PdcThen, then
Pdc=nPn (11)
The resistance element value corresponding to each submodule can be obtained as follows:
each submodule is internally provided with a separate resistor RnThe energy dissipation resistor is connected with two parallel IGBTs in series, the conduction voltages of the IGBTs are set to be different, and therefore when the direct current voltage rises, the IGBTs are gradually conducted according to the rise of the voltage, and the energy dissipation resistor is gradually put into use. Setting when direct current voltage exceeds a design threshold value U'dcAt that time, the modular energy consuming circuit begins to be triggered. Faults with different severity degrees can generate different power difference delta P, and the modularized energy consumption circuit can obtain the number n of the sub-modules which need to be put into the modularized energy consumption circuit at present according to the power difference delta P at the momenta. Through the design, the capacity of the energy consumption resistor of each submodule is only 1/n of the original direct current energy consumption resistor, and the defect that the original direct current energy consumption resistor is the largest is overcome. The more the number of the designed submodules is, the smaller the resistance capacity corresponding to each submodule is, and the heat dissipation of the resistor is more facilitated.
Further, in the third step, on the basis of the modular energy consumption resistor designed in the second step, the output power of the wind turbine generator is adjusted by combining a fault ride-through coordination control strategy designed by the wind turbine generator.
In order to realize the balance of active power during the fault period, the active output of the wind power plant is simultaneously adjusted on the basis of the modularized energy consumption resistor, so that the wind turbine generator can smoothly pass through the fault. Therefore, the active power outer ring of the rotor side frequency converter of the doubly-fed wind turbine generator is improved.
For a doubly-fed wind generator, the following relationships apply:
wherein, PsRepresenting the active power, P, output by the stator of a doubly-fed wind generatoreRepresenting the electromagnetic power of the generator, Pcus、PfesDenotes the stator copper and iron losses, Pm、P′mRepresenting input mechanical power and mechanical power losses, P, of doubly-fed machinesmecRepresenting the net mechanical power absorbed by the doubly fed machine and s representing the slip.
In order to realize the maximum power tracking of the wind turbine, the optimal power curve of the wind turbine and the wind turbine rotating speed omega are usedrTo calculate the active power command P output by the generator in real time*To output mechanical power P by fanwInstead of P in the formula (13)mCan obtain
Wherein, CpRepresenting the wind energy utilization factor, p representing the air density, S representing the area swept by the fan blades, and v representing the wind speed.
When a coordinated fault ride-through strategy is adopted, a fault occurs at the power grid side, and the direct-current voltage exceeds a set threshold value U'dcCalculating the number n of submodules to be put inaAnd because the number of the modules is an integer, the residual power can not be consumed, a new power shortage can be generated at the moment, the part is borne by the load shedding operation of the wind turbine generator, and the new power shortage delta P*=ΔP-naPnAt this time, a load shedding instruction and a new instruction value P are sent to the wind power plant1 *=P*-ΔP*The wind turbine generator system does not operate according to a maximum power curve any more, but performs load shedding operation, the electromagnetic torque of the wind turbine generator system is reduced, the rotating speed of the fan can be temporarily increased, but most of power shortage is consumed by the energy dissipation resistor when the wind turbine generator system is matched with the energy dissipation resistor, the load shedding instruction value obtained by the wind turbine generator system is small, the rotating speed increasing value of the fan is limited, and the wind turbine generator system can stably pass through faults. A schematic diagram of a modified part of the rotor-side frequency converter is shown in fig. 5.
The present invention will be described in detail with reference to the following examples and drawings.
Examples
At 4s, when a three-phase ground fault occurs at the PCC in fig. 3, the voltage drops from 1p.u. to 0.2p.u., as shown in fig. 6, the duration is 625ms, comparing the case of using the coordinated control strategy with the case of not using the coordinated control strategy. When the coordination control strategy is not adopted, the voltage change situation of the direct current bus is shown in fig. 7, the active power and the reactive power transmitted by the power grid side converter station are shown in fig. 8, and the active power and the reactive power transmitted by the wind farm side converter station are shown in fig. 9. Fig. 7 shows a change situation of the dc bus voltage after the voltage at the receiving PCC drops, where the dc bus voltage rapidly rises due to the active power imbalance because the active transmission capability of the GSVSC drops. Fig. 8 shows the active power and reactive power changes transmitted by the GSVSC, the active power transmitted during the fault decreases, and after the fault, the energy stored by the dc capacitor and the active power absorbed by the WFVSC are transmitted to the grid through the GSVSC, so that the active power transmitted to the grid at the moment of fault recovery increases instantaneously, and the bus voltage does not return to normal until the bus voltage drops to the rated value. The WFVSC transmits active and reactive power, which is almost constant because the WFVSC still receives wind farm transmission power and transfers power to the GSVSC during a fault, as shown in fig. 9. According to the simulation result, if no measures are taken during the fault period, the voltage of the direct current bus is increased, great impact is generated on the power grid, and the stable operation of the power grid is not facilitated. After the coordination control strategy is adopted, the change situation of the direct current bus voltage is shown in fig. 10, the change situations of active power and reactive power transmitted by the converter stations on the grid side and the wind farm side are shown in fig. 11 and 12, and the output situation of the wind turbine is shown in fig. 13. Fig. 10 shows the variation of the dc bus voltage, which has a small fluctuation value, and achieves a very smooth fault ride-through effect. At this time, most of the differential power is consumed by the energy consumption resistor, so that the active load shedding of the DFIG is not obvious, and therefore, as can be seen from fig. 13, the power output by the wind turbine generator is gradually reduced during the fault period, the output is gradually increased after the fault is recovered, and the instantaneous increase and decrease are not caused. Fig. 12 shows the active power and the reactive power transmitted by the GSVSC, and as can be seen by comparing with fig. 9, the fluctuation of the power is reduced, and the active power output by the GSVSC is relatively smooth. Fig. 11 shows the real and reactive power transmitted by the WFVSC, and during a fault, the transmitted real power is reduced correspondingly, while the reactive power is not changed much.