You signed in with another tab or window. Reload to refresh your session.You signed out in another tab or window. Reload to refresh your session.You switched accounts on another tab or window. Reload to refresh your session.Dismiss alert
LDmicroGitHub edited this page Oct 21, 2017
·
2 revisions
Original "TOF 2.3V.ld"
We can see Yled1 - output of the T2 TOF timer.
Modified 1 "TOF 2.3V modified 1.ld"
We can see Y1 - input of the T2 TOF timer. But it wrong.
Y1 was reset, but TOF can see input low level in next PLC cycle, after 10 ms.
Modified 2 "TOF 2.3V modified 2.ld"
Real Y1 - input of the T2 TOF timer.
So, v2.3 TOF shorter than those specified in the LD file at one PLC cycle time.