Optimized Economizer Control with Maximum Limit Set-Point to Enhance Cooling Energy Performance in Korean Climate
<p>OA intakes by varying MLSP.</p> "> Figure 2
<p>Flow chart of overall research methodology.</p> "> Figure 3
<p>Schematic of simulation baseline model: (<b>a</b>) 3D view of simulation building envelope; (<b>b</b>) simplified simulation HVAC system.</p> "> Figure 4
<p>Hourly OA intake rates by varying MLSP.</p> "> Figure 5
<p>MA conditions by varying MLSP: (<b>a</b>) MA dry-bulb temperature; (<b>b</b>) MA absolute humidity.</p> "> Figure 6
<p>Cooling coil loads by varying MLSP.</p> "> Figure 7
<p>Cooling energy consumption by varying MLSP.</p> "> Figure 8
<p>Indoor thermal environment by varying MLSP: (<b>a</b>) indoor air dry-bulb temperature; (<b>b</b>) indoor air relative humidity.</p> "> Figure 9
<p>Cooling energy consumption for each month by varying MLSP.</p> ">
Abstract
:1. Introduction
- Economizer control methods: Economizer controls have conventionally utilized fixed control for small buildings and differential control for medium and large buildings.
- Limitations in system performance analysis based on MLSP determination: Evaluations of the indoor thermal environment (e.g., dry-bulb temperature and humidity) and cooling energy performance (including OA intakes, air conditions in AHUs, and dehumidification) have not adequately addressed variations in MLSP [21,22].
2. Methodology
2.1. Overall Study Process
2.2. Simulation Modeling
2.2.1. Baseline Model
2.2.2. Determination of Simulation Cases
3. Results and Analysis
3.1. Evaluation of Cooling Energy Performance
3.1.1. OA Intakes
3.1.2. MA Conditions
3.1.3. Cooling Coil Loads
3.1.4. Cooling Energy Consumption
3.2. Evaluation of Indoor Thermal Environment
3.3. Determination of Optimal MLSP During Interseason
4. Conclusions
- (1).
- Cooling energy performance: Evaluation revealed that Case #5 had the lowest cooling energy consumption among all cases during the primary evaluation period in October. Compared to Case #1 (baseline), which set the MLSP based on ASHRAE Standard 90.1-2019, Case #5 used approximately 5.9% less cooling energy. This indicates that the MLSP of Case #5 provided the most optimal OA intake conditions. The average MA temperature in Case #5 was approximately 0.58 °C lower than that of Case #1. When the MLSP was set for Cases #1 to #4, these did not intake OA under available conditions, whereas Cases #6 and #7 maintained OA intake at conditions where the OA temperature exceeded indoor air temperature. Owing to these differences, Case #5 achieved energy savings compared to the other cases.
- (2).
- Indoor thermal environment: Evaluation showed that the indoor air dry-bulb temperature was maintained below the cooling set-point temperature in all simulation cases. Additionally, indoor relative humidity exhibited a decreasing trend as OA intakes increased. Therefore, this study suggests that raising the MLSP did not adversely affect the indoor thermal environment.
- (3).
- Optimal MLSP for interseason: The evaluation of the optimal MLSP for each month in the interseason (March, April, May, and November) indicated that optimal MLSPs were as follows: Cases #2 to #7 in March, Case #6 in April, Case #5 in May, and Cases #3 to #7 in November. This variation was due to monthly changes in OA conditions, necessitating the application of an appropriate MLSP for each month’s specific OA conditions.
Author Contributions
Funding
Institutional Review Board Statement
Informed Consent Statement
Data Availability Statement
Conflicts of Interest
Abbreviations
AHU | air handing unit |
OA | outdoor air |
MLSP | maximum limit set-point |
MA | mixed air |
RA | return air |
HVAC | heating, ventilation, and air conditioning |
WWR | window-to-wall ratio |
VAV | variable-air-volume |
IWEC2 | international weather files for energy calculation 2.0 |
References
- Yoon, Y.; Seo, B.; Cho, S. Potential Cooling Energy Savings of Economizer Control and Artificial-Neural-Network-Based Air-Handling Unit Discharge Air Temperature Control for Commercial Building. Buildings 2023, 13, 1174. [Google Scholar] [CrossRef]
- Dharmasena, P.; Nassif, N. Testing; Validation, and Simulation of a Novel Economizer Damper Control Strategy to Enhance HVAC System Efficiency. Buildings 2024, 14, 2937. [Google Scholar] [CrossRef]
- Kim, C.H.; Lee, S.C.; Park, K.S.; Lee, K.H. Analysis of thermal environment and energy performance by biased economizer outdoor air temperature sensor fault. J. Mech. Sci. Technol. 2022, 36, 2083–2094. [Google Scholar] [CrossRef]
- Lee, K.; Chen, H. Analysis of energy saving potential of air-side free cooling for data centers in worldwide climate zones. Energy Build. 2013, 64, 103–112. [Google Scholar] [CrossRef]
- Ham, S.; Kim, M.; Choi, B.; Jeong, J. Energy saving potential of various air-side economizers in a modular data center. Appl. Energy 2015, 138, 258–275. [Google Scholar] [CrossRef]
- Ghiaus, C.; Allard, F. Potential for free-cooling by ventilation. Solar Energy 2006, 80, 402–413. [Google Scholar] [CrossRef]
- Mu, B.; Li, Y.; House, J.M.; Salsbury, T.I. Experimental evaluation of anti-windup extremum seeking control for airside economizers. Control. Eng. Pract. 2016, 50, 37–47. [Google Scholar] [CrossRef]
- Trane, Airside Economizers and Their Application. 2015. Available online: https://www.trane.com/content/dam/Trane/Commercial/global/products-systems/education-training/engineers-newsletters/airside-design/ADM-APN054-EN_05202015.pdf (accessed on 22 January 2025).
- Hong, G.; Kim, C. Investigation of energy savings potential of multi-variable differential temperature control in economizer. Appl. Therm. Eng. 2021, 197, 117415. [Google Scholar] [CrossRef]
- Seem, J.E.; House, J.M. Development and evaluation of optimization-based air economizer strategies. Appl. Energy 2010, 87, 910–924. [Google Scholar] [CrossRef]
- Wang, S.K. Handbook of Air Conditioning and Refrigeration, 2nd ed.; McGraw-Hill Companies Inc.: New York, NY, USA, 2001. [Google Scholar]
- Kim, M.; Jin, S.; Jang, A.; Park, B.; Do, S.L. Simulated analysis on cooling system performance influenced by faults occurred in enthalpy sensor for economizer control. In Proceedings of the 10th International Conference on Construction Engineering and Project Management (ICCEPM), Sapporo, Japan, 29 July–1 August 2024; pp. 1002–1009. [Google Scholar] [CrossRef]
- Kim, J.H.; Shin, D.U.; Kim, H. Data Center Energy Evaluation Tool Development and Analysis of Power Usage Effectiveness with Different Economizer Types in Various Climate Zones. Buildings 2024, 14, 299. [Google Scholar] [CrossRef]
- Zhou, J.; Wei, G.; Turner, W.D.; Claridge, D.E. Airside economizer—Comparing different control strategies and common misconceptions. In Proceedings of the Sixteenth Symposium on Improving Building Systems in Hot and Humid Climates, Plano, TX, USA, 15–17 December 2008; Texas A&M University: College Station, TX, USA, 2008. Available online: https://hdl.handle.net/1969.1/90706 (accessed on 22 January 2025).
- Taylor, S.T.; Cheng, C.H. Economizer High Limit Controls and Why Enthalpy Economizers Don’t Work. Am. Soc. Heat. Refrig. Air-Cond. Eng. (ASHRAE) 2010, 52, 12–28. [Google Scholar]
- Chowdhury, A.A.; Rasul, M.G.; Khan, M.M.K. Modelling and analysis of air-cooled reciprocating chiller and demand energy savings using passive cooling. Appl. Therm. Eng. 2009, 29, 1825–1830. [Google Scholar] [CrossRef]
- Li, B.; Wild, P.; Rowe, A. Free cooling potential of air economizer in residential houses in Canada. Build. Environ. 2020, 167, 106460. [Google Scholar] [CrossRef]
- Badiei, A.; Jadowski, E.; Sadati, S.; Beizaee, A.; Li, J.; Khajenoori, L.; Nasriani, H.R.; Li, G.; Xiao, X. The energy-saving potential of air-side economisers in modular data centers: Analysis of opportunities and risks in different climates. Sustainability 2023, 15, 10777. [Google Scholar] [CrossRef]
- Wang, G.; Song, L. An energy performance study of several factors in air economizers with low-limit space humidity. Energy Build. 2013, 64, 447–455. [Google Scholar] [CrossRef]
- Song, R.; Liu, D.; Pan, Y.; Cheng, Y.; Meng, C. Container farms: Energy modeling considering crop growth and energy-saving potential in different climates. J. Clean. Prod. 2023, 420, 138353. [Google Scholar] [CrossRef]
- Seong, N.; Hong, G. Evaluation of Operation Performance Depending on the Control Methods and Set Point Variation of the Economizer System. J. Korean Inst. Archit. Sustain. Environ. Build. Syst. 2022, 16, 94–107. [Google Scholar] [CrossRef]
- Choi, B.; Kim, H.; Cho, Y. A study on Performance Evaluation of Economizer Type through Simulation in Office. J. Korean Inst. Archit. Sustain. Environ. Build. Syst. 2015, 9, 229–234. [Google Scholar]
- Yao, Y.; Wang, L. Energy analysis on VAV system with different air-side economizers in China. Energy Build. 2010, 42, 1220–1230. [Google Scholar] [CrossRef]
- Lee, J.; Jo, H.; Cho, Y. Mixed air temperature reset by data-driven model for optimal economizer control. Appl. Therm. Eng. 2024, 238, 122158. [Google Scholar] [CrossRef]
- Son, J.E.; Lee, K.H. Cooling energy performance analysis depending on the economizer cycle control methods in an office building. Energy Build. 2016, 120, 45–57. [Google Scholar] [CrossRef]
- ASHRAE Standard 90.1; Energy Standard for Building Except Low-Rise Residential Buildings. American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE): Atlanta, GA, USA, 2019.
- Jang, A.; Jin, S.; Kim, M.; Kang, H.; Do, S.L. Evaluation of Cooling Energy Consumption Varying Economizer Control and Heat Generation Rates from IT Equipment in Data Center. In Proceedings of the 10th International Conference on Construction Engineering and Project Management (ICCEPM), Sapporo, Japan, 29 July–1 August 2024; pp. 1010–1017. [Google Scholar] [CrossRef]
- Lee, J.; Cho, Y. Optimal Control of Air-side Economizer. Energies 2024, 17, 5383. [Google Scholar] [CrossRef]
- DOE. EnergyPlus, Version 9.3; Department of Energy (DOE): Washington, DC, USA, 2020.
- DOE. Commercial Reference Building; Department of Energy (DOE): Washington, DC, USA, 2019.
- DOE. EnergyPlus Documentation: Input Output Reference; Department of Energy (DOE): Washington, DC, USA, 2020.
- KEA. Building Energy Efficiency Certification; Korea Energy Agency (KEA): Ulsan, Republic of Korea, 2021. [Google Scholar]
- DOE. EnergyPlus Documentation: Engineering Reference; Department of Energy (DOE): Washington, DC, USA, 2020.
- ASHRAE. International Weather for Energy Calculations Version 2.0; American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE): Atlanta, GA, USA, 2017. [Google Scholar]
Ref. | Authors | Location | Building Type | Building Total Floor Area | Economizer Control Method | MLSP |
---|---|---|---|---|---|---|
[16] | Chowdhury et al. | Rockhampton, Australia | Office | Medium (4263 m2) | N/A | N/A |
[17] | Li et al. | 17 regions in Canada 1 | Residential | Small (193 m2) | Fixed | N/A |
[18] | Badiei et al. | Stockholm, Sweden; Dubai, UAE San Francisco, US; Singapore | Datacenter | Small (12 m2) | Fixed | 24 °C |
[19] | Wang and Song | Atlanta, US | Commercial | Small (214 m2) | Differential | N/A |
[20] | Song et al. | 8 regions in China 2 | Container farm | Small (15 m2) | Fixed | N/A |
[21] | Seong and Hong | Donghae, South Korea | Education | Large (9927 m2) | Fixed and Differential | 22 °C |
[22] | Choi et al. | Daejeon, South Korea | Office | Large (6164 m2) | Fixed and Differential | 24 °C and 28 °C |
[23] | Yao and Wang | 6 regions in China 3 | Office | Medium (4646 m2) | Differential | N/A |
[24] | Lee et al. | Ulsan, South Korea | Laboratory | Small (78 m2) | Fixed | 18 °C |
[25] | Son and Lee | Incheon, South Korea Miami and Madison and San Francisco, US | Office | Medium (1859 m2) | Differential | N/A |
Input Parameters | Values | Information Source | |||
---|---|---|---|---|---|
Building | Zone | Use | Office building | ||
Floor area | 450 m2 | DOE-2 reference model | |||
Floor-to-floor height | 3 m | ||||
WWR | North and south | 0.4 | |||
East and west | 0.5 | ||||
Indoor cooling set-point | 24℃ | ASHRAE Standard 90.1-2019 | |||
Heat generation | People | 120 W/person | |||
Light | 6.89 W/m2 | ||||
Equipment | 6.78 W/m2 | ||||
System | Operation | HVAC | VAV | ||
Economizer control type | Dry-bulb temperature | ||||
Maximum OA intake rates | 100% | ||||
Minimum OA intake rates | 30% | ||||
Supply air dry-bulb temperature | 13℃ | ASHRAE Standard 90.1-2019 | |||
Supply air absolute humidity | 0.008 kg/kg’ | ||||
Operating hours | Weekdays | 07:00–18:00 | Building Energy Efficiency Certification | ||
Weekends | None | ||||
Capacity | Air-cooled chiller | 19,240 W | |||
Cooling water pump | 292 W | ||||
Variable-speed fan | 0.4 m3/s | ||||
Simulation setting | Weather data | Daejeon, South Korea | IWEC2 | ||
Run period | Interseason | ||||
Time-step | 1 min |
Simulation Cases | MLSP [°C] | References |
---|---|---|
Case #1 (basecase) | 18 | ASHRAE Standard 90.1-2019 |
Case #2 | 19 | Parametric analysis |
Case #3 | 20 | |
Case #4 | 21 | |
Case #5 | 22 | |
Case #6 | 23 | |
Case #7 | 24 |
Simulation Cases | Case #1 | Case #2 | Case #3 | Case #4 | Case #5 | Case #6 | Case #7 |
---|---|---|---|---|---|---|---|
Accumulated times of maximum OA intake rates [h] | 50 | 67 (17↑) | 83 (33↑) | 119 (69↑) | 147 (97↑) | 165 (115↑) | 174 (124↑) |
Accumulated times of partial OA intake rates [h] | 90 | 88 (2↓) | 87 (3↓) | 85 (5↓) | 74 (16↓) | 68 (22↓) | 65 (25↓) |
Accumulated times of minimum OA intake rates [h] | 102 | 87 (25↓) | 72 (30↓) | 38 (64↓) | 21 (81↓) | 9 (93↓) | 3 (99↓) |
Accumulated OA intakes [m3/s] | 51 | 56 (5↑) | 60 (9↑) | 68 (17↑) | 73 (22↑) | 77 (26↑) | 78 (27↑) |
Simulation Cases | Case #1 | Case #2 | Case #3 | Case #4 | Case #5 | Case #6 | Case #7 |
---|---|---|---|---|---|---|---|
Average MA dry-bulb temperature [°C] | 18.13 | 17.95 (0.18↓) | 17.80 (0.33↓) | 17.64 (0.49↓) | 17.55 (0.58↓) | 17.56 (0.57↓) | 17.58 (0.55↓) |
Average MA absolute humidity [kg/kg’ × 103] | 10.12 | 10.08 | 9.95 | 9.77 | 9.70 | 9.64 | 9.63 |
(0.04↓) | (0.17↓) | (0.36↓) | (0.43↓) | (0.48↓) | (0.49↓) |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2025 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
Kim, M.; Lee, C.; Jang, A.; Do, S.L. Optimized Economizer Control with Maximum Limit Set-Point to Enhance Cooling Energy Performance in Korean Climate. Appl. Sci. 2025, 15, 2825. https://doi.org/10.3390/app15052825
Kim M, Lee C, Jang A, Do SL. Optimized Economizer Control with Maximum Limit Set-Point to Enhance Cooling Energy Performance in Korean Climate. Applied Sciences. 2025; 15(5):2825. https://doi.org/10.3390/app15052825
Chicago/Turabian StyleKim, Minho, Chanuk Lee, Ahmin Jang, and Sung Lok Do. 2025. "Optimized Economizer Control with Maximum Limit Set-Point to Enhance Cooling Energy Performance in Korean Climate" Applied Sciences 15, no. 5: 2825. https://doi.org/10.3390/app15052825
APA StyleKim, M., Lee, C., Jang, A., & Do, S. L. (2025). Optimized Economizer Control with Maximum Limit Set-Point to Enhance Cooling Energy Performance in Korean Climate. Applied Sciences, 15(5), 2825. https://doi.org/10.3390/app15052825